71 8300. Fire Prevention and Life SafetyBuildings.
71 8300.1. Purpose and Definitions.
A. These regulations are for safeguarding, to a reasonable degree, life and property from fire and other hazards associated with the construction, alteration, repair, use, and occupancy of buildings, structures, or premises. These regulations shall be the minimum standards required by the State Fire Marshal for fire prevention and life safety in all buildings and structures to which they apply, except when they conflict with any existing state statutes.
B. "Existing Building" means a building, structure, or premise for which preliminary or final drawings have been approved by the appropriate agency as provided in these regulations, or buildings where construction has begun, or those occupied on or before the date of adoption of these regulations.
C. "Fire Control" means all activities to control hostile fires.
D. "Fire Prevention" means any activity to prevent fire before fire occurs.
E. "SMC" means the Standard Mechanical Code.
F. "NEC" means National Electrical Code NFPA 70.
G. "NFPA" means the National Fire Protection Association.
H. "SBC" means the Standard Building Code.
I. "SFPC" means the Standard Fire Prevention Code.
J. "UL" means Underwriters' Laboratories, Inc.
K. "NFPA 101" means the Life Safety Code.
71 8300.2. Application to Construction, Installation, Alterations, and Repairs.
No building or structure shall be constructed, altered, or repaired, nor shall the equipment of a building, structure, or premise be constructed, installed, altered, or repaired except in conformity with these regulations. Existing buildings shall be exempt from these regulations unless otherwise indicated.
71 8300.3. Occupancy.
No one shall occupy or use a building, structure, or part of a building erected or altered in violation of these regulations.
71 8300.4. Effect.
These regulations shall apply with equal force to municipal, county, state, and private buildings, except as provided in these regulations.
71 8300.5. Exemptions.
Nothing in 718300.9 shall apply to buildings constructed, or occupied exclusively as oneand twofamily dwellings, barns, and other farm buildings, and onestory buildings not exceeding five thousand square feet in area, other than those used for assembly, educational, institutional, domiciliary (R1 or R2), or hazardous occupancies.
71 8300.6. Enforcement.
Reserved for future use.
71 8300.7. Submission of Plans, Specifications, and Reports.
A. Plans and Specifications.
1. Where work contemplated is regulated by these regulations and enforced by the State Fire Marshal, plans and specifications shall be submitted to the State Fire Marshal or his designee for approval prior to starting such work. Where required by state licensing and regulatory provisions, such plans and specifications shall be prepared by a duly registered architect and/or engineer.
2. Submitted plans, calculations, and specifications for all buildings, structures, systems, or premises shall provide sufficient information to indicate how compliance with state law, regulations, and adopted codes enforced by the State Fire Marshal's Office will be accomplished. Codes shall not be cited in whole or part as a substitute for providing specific information.
3. The State Fire Marshal or other approving authority may revoke any approval issued under the provisions of these regulations where the approval was based on any false statement or misrepresentation of fact in correspondences, plans, specifications, or data.
B. Reporting System.
The local fire chief or his designee shall, within one calendar month of any fire, furnish the State Fire Marshal with a written statement of all the facts relating to its cause, its origin, the kind, the estimated value, ownership of the property damaged or destroyed, and other information called for by the forms furnished by the State Fire Marshal. The fire chief may report to the State Fire Marshal using an electronic format approved by the State Fire Marshal.
71 8300.8. Existing Buildings.
A. Alterations, repairs, or rehabilitation work may be done to an existing building, structure, electrical, gas, mechanical, or fire protection system without requiring the entire building, structure, electrical, gas, mechanical, or fire protection system to comply with all the requirements of the adopted codes, provided the work conforms to the requirements of these regulations for new construction.
B. If within any period of twelve months, additions, alterations, or repairs costing more than fifty percent of the appraised market value of the building, excluding land value and site improvements, are made to an existing building, such existing building shall conform with these regulations for the construction of new buildings.
C. If an existing building is damaged by fire, or otherwise, in excess of fifty percent of the appraised market value immediately preceding such damage, when such damage is repaired, the entire building shall conform to the requirements of these regulations for the construction of new buildings.
D. If the occupancy of an existing building is changed, the entire building shall conform to the requirements of these regulations for the new occupancy. If the occupancy of only a portion of an existing building is changed, and that portion is separated from the remainder of the building per 718300.9, then only that portion of the building must be made to conform. A change of occupancy shall be considered new construction for the application of these regulations.
E. All new and existing buildings or structures and all parts shall be maintained in a safe condition. All devices and safeguards required by these regulations in a building when erected, altered, or repaired shall be maintained in good working order. The owner or his designated agent is responsible for the maintenance of buildings and structures.
F. The provisions of these regulations relating to the construction, alteration, repair, enlargement, restoration, relocation, or moving of buildings or structures shall not be mandatory for existing buildings or structures listed on national, state, or local historical registers. The State Fire Marshal has authority to approve alternate methods of compliance within the intent of the regulations.
G. Existing shortterm rental units must comply with 718300.11.
71 8300.9 Fire Prevention and Life Safety Standards for Construction, Occupancy, and Use and Adoption of the Standard Building Code.
A. Minimum standards for fire prevention and life safety protection in construction, occupancy, and use of all buildings and structures within the scope of these regulations shall be the following chapters and sections of the 1997 edition of the Standard Building Code.
1. Chapter 2;
2. Chapter 3 (omit 306.1.2 and Group R4 occupancies in 311.2);
3. Chapter 4;
4. Chapter 5 (omit 505);
5. Chapter 6;
6. Chapter 7;
7. Chapter 8;
8. Chapter 9 (omit 903.7.7);
9. Chapter 10;
10. Section 1517;
11. Section 1709;
12. Chapter 28;
13. Sections 3104 and 3106; and
14. Chapter 35.
B. All references to the SBC found in these regulations refer to the edition adopted above. All references to NFPA Standards found in these regulations refer to the editions specified in the SBC unless otherwise stated in these regulations.
71 8300.10. Installation of Electrical Equipment and Systems.
The provisions of NFPA 70, 1996 edition, shall constitute the minimum general standards covering fire prevention and protection of persons and property from hazards from the use of electricity.
71 8300.11. Special Code Provisions which Prevail Over 718300.9 and 718301.3.B.
A. Fire Alarm Systems.
1. Facilities with fire alarm systems shall be designed, installed, and maintained per the 1996 edition of NFPA 72.
2. Fire alarm systems shall provide off premises notification to the fire department per NFPA 72 for day care centers and schools serving more than one hundred clients, hazardous occupancies, institutional occupancies, and adult residential care facilities licensed for thirteen or more residents.
B. Facilities with Infant Care.
1. This section applies to new construction and is retroactively applied to all infant care facilities within the scope of these regulations. In retroactive applications, the State Fire Marshal has authority to approve alternate methods of compliance within the intent of the regulations.
2. All facilities in South Carolina which provide care for four or more children, twentyfour months of age and under, and who are unattended by a parent or guardian, shall provide the following safeguards. Children under the age of twentyfour months are defined as infants.
a. Rooms for infants shall have onehour fire separation with a direct exit to the outside. No fire rated separation is required between adjacent infant rooms.
b. Rooms for infants shall have wall covering with a flamespread rating no less than Class C.
c. Rooms used for infants shall not have any type of open flame appliances. Any recirculating air ducts entering the room shall be protected by smoke dampers operated by a smoke sensor or automatic smoke actuated shutdown of air handling equipment per NFPA 90A. Fire dampers shall be installed per the SBC and the SMC.
d. Rooms for infants shall be limited to twelve infants per direct exit. There shall be no more than twentyfour infants per room. If older children are kept in the infant room, they shall be counted as infants for direct exits and room occupancy considerations. Exit doors shall swing in the direction of egress and be a minimum of thirtysix inches wide.
e. Rooms for infants shall have single station smoke alarms placed inside the room and in the adjacent area of the facility near the protected room's entrance. Smoke detectors shall be installed and maintained per NFPA 72.
f. Doors in the required onehour separation partitions shall be twentyminute labeled doors equipped with door closures or a smoke actuated holdopen device.
g. A fire plan describing what actions are to be taken by the staff in the event of a fire must be developed, posted, and copies made available to all employees and local fire authorities.
h. A fire drill shall be conducted at least every three months. The owner shall maintain records of drills for three years. Records shall report the date, time, and a description and evaluation of each drill. Fire drills shall include complete evacuation of all persons from the building.
C. Special Requirements for Hospitals, Nursing Homes, and Intermediate Care Facilities.
1. Renovations of existing facilities shall include the addition of fire protection sprinklers. All new construction must be fully sprinklered. All other requirements of this section apply to new construction and retroactively to existing construction unless otherwise specified.
2. In existing facilities, enclosures for stairways, elevator shafts, chutes, and other vertical shafts shall be of not less than twohour fire resistive construction. Compliance with the SBC is acceptable for new construction.
3. In existing facilities, service openings to chutes, dumbwaiters, conveyors, and other material handling systems shall not be located in corridors or passageways but shall be located in a room enclosed by construction having at least a onehour fire resistive rating. Doors to such rooms shall not be less than Class C labeled, 3/4hour fire rated. Service entrance doors to chutes and vertical shafts containing dumbwaiters, conveyors, and material handling systems shall be not less than Class B labeled, 1 1/2 hour fire rated and shall be selfclosing. Compliance with the SBC is acceptable for new construction.
4. Gases (flammable and nonflammable) shall be handled and stored per the applicable provisions of NFPA 99, 1996 edition.
5. Flammable and combustible liquids shall be stored and handled per NFPA 30, 1996 edition.
6. Fire extinguishers intended for use in patient areas shall be of the 2A, two and onehalf gallon storedpressure water type. A 4A: 40BC minimum classification fire extinguisher shall be installed in the following hazardous areas: kitchen, laundry room, and any other area having an unusual fire hazard. At least one 2A: 10 BC minimum classification fire extinguisher shall be located at each nurse's station.
7. Existing facilities shall provide an electrically supervised manual fire alarm system per the provisions found in the NFPA standard in effect at the time of first licensure.
8. Each existing facility having more than ten beds must have a manual fire alarm system per the provisions of the NFPA standard in effect at the time of first licensure. The system shall be connected either directly or through a central station facility to the public fire department or other outside assistance as may be available in case of fire or other emergency.
9. In existing facilities, an approved automatic smoke detection system shall be installed in all corridors. Such system shall be installed per the NFPA standards in effect at the time of first licensure. Smoke detectors shall not be spaced farther apart than thirty feet on centers or more than fifteen feet from any wall. The system shall be electrically interconnected to the fire alarm system as well as to all holdopen devices on smoke doors and fire doors within a fire zone.
EXCEPTION: Where each patient sleeping room is protected by such an approved detection system and a local detection device is provided at each smoke door, such corridor system shall not be required on the patient sleeping room floors. This requirement does not apply to facilities constructed prior to April 23, 1979.
10. In all facilities, smoke doors within a fire zone shall automatically close upon actuation of the manual fire alarm system, waterflow, or activation of the automatic sprinkler or fire suppression system, or any automatic detection devices in that fire zone.
EXCEPTION: Elevator Recall for Fire Fighters' Service installed per NFPA 72.
11. In all facilities, a fire protection plan describing what actions are to be taken by the staff in event of a fire must be developed and copies made available to all employees and the local fire authority.
12. Each employee shall receive initial fire protection training on the following:
a. the fire plan;
b. how to report a fire;
c. how to use the fire alarm system;
d. the location and use of fire fighting equipment;
e. methods of fire containment;
f. specific responsibilities of the individual as well as other individuals.
13. A fire drill shall be conducted for each shift at least once every three months. Records shall be maintained to report the date, time, shift, description, and evaluation of the drill.
14. In new construction, the fire alarm systems must comply with the requirements of SBC and NFPA 72.
15. Hospitals and nursing homes must maintain compliance with all SBC, NFPA, and SFPC requirements in effect at the time of first licensure.
D. Specific Requirements for Adult Residential Care Facilities.
1. Unless otherwise indicated, all requirements of this section apply to new construction and apply retroactively to adult residential care facilities. In retroactive applications, the State Fire Marshal has authority to approve alternate methods of compliance within the intent of the regulations.
2. Adult residential care facilities are defined as buildings, structures, or any portion thereof, used for providing boarding and lodging facilities for twentyfour or more consecutive hours to persons who are aged, physically, mentally, or developmentally disabled, and persons who may need a degree of personal care or supervision.
a. All residents shall be capable of selfevacuation within three minutes of an alarm. Residents not capable of selfevacuation within three minutes are considered incapable of selfpreservation.
b. Facilities complying with the requirements of Intermediate Care Facilities Mental Retardationfifteen beds or less (ICFMR15) may house up to three residents incapable of selfpreservation.
c. ICFMR15 compliant facilities and adult residential care facilities housing four or more residents incapable of selfpreservation must be sprinklered per NFPA 13.
d. Full compliance with NFPA 101, 1997 edition, "Board and Care Facilities" standards is an acceptable alternative to an NFPA 13 sprinkler system, unless an NFPA 13 sprinkler system is required elsewhere in state statute, regulations, or adopted codes.
e. Residents incapable of selfpreservation may not be located above or below the level of exit discharge.
f. The fire alarm system shall transmit an alarm automatically to the fire department serving the facility and shall comply with the appropriate NFPA standard.
3. All adult residential care facilities licensed for five or fewer residents shall meet all requirements for R3 Occupancies per the SBC and have:
a. Single station smoke detectors installed in the hallways and within every sleeping room per NFPA 72;
b. Backup powered emergency lights installed to light exit egress;
c. Heating devices:
i. All heating devices must be selected, used, and installed per the applicable NFPA standard, the manufacturer's recommendations, and listing conditions set by an approved testing laboratory;
ii. Portable electric heaters may be used for emergencies and supplemental heating. Portable heaters in client areas shall be guarded to prevent burn injuries. The maximum exposed surface temperatures for portable electric heaters shall not exceed 68 degrees F for metallic parts and 108 degrees F for nonmetallic parts;
iii. Unguarded open flame heaters may be used only during emergencies when electrical power is not available;
iv. Unvented gas heaters shall have an operating oxygen depletion device and an operating safety shutoff device;
d. Fire extinguishers shall be sized, installed, and maintained per NFPA 10;
e. Drapes or curtains not constructed of flame resistant material shall be treated and maintained fire resistant per the manufacturer's instructions;
f. In areas not protected by a fire department, a contract with the nearest fire department shall be secured if possible;
g. Extension cords are permitted only with portable appliances or fixtures as allowed by the NEC;
h. Manufactured housing, mobile homes, or campers are prohibited for residential care;
i. A telephone is required. A coin operated telephone will not meet this requirement;
j. Smoking will be allowed only in designated areas. No smoking is permitted in the bedrooms;
k. One safety ramp shall be installed for facilities serving handicapped clients;
l. A fire drill shall be conducted at least every three months. Records shall be maintained for three years and report the date, time, description, and evaluation of each drill. Fire drills shall include complete evacuation of all persons from the building and;
m. A fire plan describing what actions are to be taken by the staff in the event of a fire or other emergency must be developed. This plan shall note the location of all clients temporarily incapable of selfpreservation. The plan shall be posted and copies made available to all employees and the local fire authority.
4. All adult residential care facilities licensed for six to twelve residents shall meet the requirements for R2 Occupancies per SBC, the requirements of 718300.11.D.3 above and the following:
a. All partitions that separate sleeping rooms or that separate sleeping rooms from other portions of the building shall be of not less than onehour fire resistant construction. Fire rated separations shall be constructed per the SBC; and
b. For facilities equipped with an automatic sprinkler and a fire alarm system, door closures on individual sleeping rooms may be omitted.
5. All adult residential care facilities licensed for thirteen or more residents shall meet all the requirements in 718300.11.D.3 and 718300.11.D.4 in addition to:
a. Facilities shall have an approved underhood automatic extinguishing system in the kitchen;
In the alternative the owner may adopt a controlled cooking plan. The owner shall submit a letter to the State Fire Marshal confirming there will be no surface or deep fat frying done in the facility. The owner will post a sign over the stove stating this policy. Failure to follow the controlled cooking plan will require installation of a commercial hood system with an automatic fire extinguishing system.
b. No resident bedroom shall be approved if access is through kitchen, bathrooms, closets, or similar spaces;
c. In existing facilities:
i. Smoke detectors shall be installed in each sleeping room. When more than one smoke alarm is required, they shall all be tied together as a system so when one smoke detector is activated, all smoke alarms will activate to alert all persons in the building. All smoke detection systems shall be one hundred ten volt type with battery or auxiliary power backup. These systems shall comply with NFPA 72A, 1997 edition, and 72E, 1997 edition. All system components shall be UL listed and installed per the conditions of their listing and the manufacturer's recommendations; or
ii. A fire alarm system complying with NFPA 72 will be accepted; and
d. In new facilities, fire alarm systems must comply with the requirements of SBC and NFPA 72.
E. Child and Adult Day Care Facilities.
1. All child and adult day care facilities with thirteen or more clients receiving care, maintenance, and supervision for less than twentyfour hours but more than four hours per day shall be considered educational occupancy and comply with the following requirements. Child day care facilities with four or more infants shall comply with the requirements of 718300.11.B., Facilities with Infant Care.
a. A listed smoke detector shall be installed and maintained per NFPA 72 in every room occupied by clients excluding bathrooms. Existing facilities may use single station smoke detectors.
b. Special protective covers for electrical receptacles shall be installed on all receptacles located in areas occupied by clients.
c. Facilities shall have an approved underhood automatic extinguishing system in the kitchen.
In the alternative the owner may adopt a controlled cooking plan. The owner shall submit a letter to the State Fire Marshal confirming there will be no surface or deep fat frying done in the facility. The owner will post a sign over the stove stating this policy. Failure to follow the controlled cooking plan will require installation of a commercial hood system with an automatic fire extinguishing system.
2. All adult day care facilities with twelve or fewer clients receiving care, maintenance, and supervision for less than twentyfour hours but more than four hours per day shall be considered residential occupancy.
3. A fire drill shall be conducted at all child and adult day care facilities per the SFPC for educational occupancies. Records of drills shall be maintained for a period of three years and report the date, time, description, and evaluation of each drill. Fire drills shall include complete evacuation of all persons from the building.
4. A fire plan describing what actions are to be taken by the staff of child and adult day care facilities in the event of a fire or other emergency must be developed. This plan shall note the location of all crib infants in child day care facilities. The plan shall be posted and copies made available to all employees and the local fire authority.
5. Places of worship which operate a nursery for the care of children and/or infants during worship services or for other church related activities, provided these activities do not last longer than four hours, are exempt from child and/or infant care regulations.
6. All child group day care facilities with at least seven clients but not more than twelve clients receiving care, maintenance, and supervision for less than twentyfour hours but more than four hours per day shall be considered residential occupancy and comply with the following requirements:
a. Mixed occupancies
i. Group day care facilities shall be separated from other type occupancies (excluding owner residence) by a onehour fire barrier constructed per the SBC.
ii. All group day care facilities located in R2 occupancies shall be located on the floor of exit discharge.
b. Exits
i. Each group day care facility occupied by clients shall have at least two independent means of escape as defined in NFPA 101, 1997 edition; and
ii. Group day care facilities for clients in the first grade or younger must be located on a floor of exit discharge.
c. Special Requirements
i. The doorway between the level of exit discharge and any floor below shall be equipped with a selfclosing 1 3/4 "' solid core wood door or a labeled fire rated door;
ii. Group day care is prohibited in manufactured housing (mobile homes);
iii. A fire plan describing what actions are to be taken by the staff in the event of a fire must be developed, posted, and copies made available to staff members and the local fire department. This plan shall note the location of all crib infants; and
iv. A fire drill shall be conducted per the SFPC for educational occupancies. Records of drills shall be maintained for a period of three years and report the date, time, description, and evaluation of each drill. Fire drills shall include complete evacuation of all persons from the building.
d. The interior finish in occupied spaces and exits in group day care facilities shall be a minimum of Class C.
e. A listed smoke detector shall be installed and maintained per NFPA 72 in every room occupied by clients excluding bathrooms.
f. At least one portable fire extinguisher with a minimum classification of 2A: 10BC shall be installed in cooking areas. Fire extinguishers shall be maintained per NFPA 10.
g. Special protective covers for electrical receptacles shall be installed on all receptacles located in areas occupied by clients.
h. Heating devices
i. All heating devices must be selected, used, and installed per the applicable NFPA standard, the manufacturer's recommendations, and listing conditions set by an approved testing laboratory;
ii. Portable electric heaters may be used for emergencies and supplemental heating. Portable heaters in client areas shall be guarded to prevent burn injuries. The maximum exposed surface temperatures for portable electric heaters shall not exceed 68 degrees F for metallic parts and 108 degrees F for nonmetallic parts;
iii. Unguarded open flame heaters may be used only during emergencies when electrical power is not available;
iv. Unvented gas heaters shall have an operating oxygen depletion device and an operating safety shutoff device; and
v. Fireplaces shall be equipped with fire screens, partitions, or other means to protect clients from burns.
i. Group day care facilities with four or more infants shall comply with the requirements of 718300. 11.B., Facilities with Infant Care.
7. All child family day care facilities that require licenses, with six or fewer clients receiving care, maintenance, and supervision for less than twentyfour hours but more than four hours per day shall be considered residential occupancy and comply with the following requirements:
a. Mixed occupancies
i. Child family day care facilities shall be separated from other type occupancies (excluding owner residence) by a onehour fire barrier constructed per the SBC; and
ii. Child family day care facilities located in R2 occupancies shall be located on the floor of exit discharge.
b. Exits
i. Each child family day care facility occupied by clients shall have at least two independent means of escape as defined in NFPA 101, 1997 edition; and
ii. Child family day care facilities for clients in the first grade or younger must be located on a floor of exit discharge.
c. Special requirements
i. The doorway between the level of exit discharge and any floor below shall be equipped with a selfclosing 1 3/4 "' solid core wood door or a labeled fire rated door;
ii. A fire plan describing what actions are to be taken by the staff in the event of a fire must be developed, posted, and copies made available to staff members and the local fire department. This plan shall note the location of all crib infants; and
iii. A fire drill shall be conducted every three months. Records of drills shall be maintained to report the date, time, description, and evaluation of each drill. Fire drills shall include complete evacuation of all persons from the building.
d. The interior finish in occupied spaces and exits in child family day care facilities shall be a minimum of Class C.
e. A listed smoke detector shall be installed and maintained per NFPA 72 in every room occupied by clients excluding bathrooms.
f. At least one portable fire extinguisher with a minimum classification of 2A: 10BC shall be installed in cooking areas.
g. Special protective covers for electrical receptacles shall be installed on all receptacles located in areas occupied by clients.
h. Heating devices
i. All heating devices must be selected, used, and installed per the applicable NFPA standard, the manufacturer's recommendations, and listing conditions set by an approved testing laboratory;
ii. Portable electric heaters may be used for emergencies and supplemental heating. Portable heaters in client areas shall be guarded to prevent burn injuries. The maximum exposed surface temperatures for portable electric heaters shall not exceed 68 degrees F for metallic parts and 108 degrees F for nonmetallic parts;
iii. Unguarded open flame heaters may be used only during emergencies when electrical power is not available;
iv. Unvented gas heaters shall have an operating oxygen depletion device and an operating safety shutoff device; and
v. Fireplaces shall be equipped with fire screens, partitions, or other means to protect clients from burns.
i. Group day care facilities with four or more infants shall comply with the requirements of 718300. 11.B., Facilities with Infant Care.
F. Foster Care Facilities.
1. Foster homes providing care, maintenance, and supervision for no more than six children, to include the natural or adopted children of the foster parent, shall be considered R3 and comply with the following requirements.
a. A listed smoke detector shall be installed and maintained per NFPA 72 in bedrooms where foster children sleep and in the hallway leading to bedrooms.
b. As a minimum, one fire extinguisher with a minimum classification of 2A:10BC shall be located in the cooking area. Fire extinguishers shall be installed and maintained per NFPA 10.
c. Each facility housing foster children shall have two independent means of escape as defined in NFPA 101, 1997 edition.
d. Heating devices
i. All heating devices must be selected, used, and installed per the applicable NFPA standard, the manufacturer's recommendations, and listing conditions set by an approved testing laboratory;
ii. Portable electric heaters may be used for emergencies and supplemental heating. Portable heaters in client areas shall be guarded to prevent burn injuries. The maximum exposed surface temperatures for portable electric heaters shall not exceed 68 degrees F for metallic parts and 108 degrees F for nonmetallic parts;
iii. Unguarded open flame heaters may be used only during emergencies when electrical power is not available;
iv. Unvented gas heaters shall have an operating oxygen depletion device and an operating safety shutoff device; and
v. Fireplaces shall be equipped with fire screens, partitions, or other means to protect clients from burns.
e. A fire plan describing what actions are to be taken by the family in the event of a fire must be developed, posted, and copies made available to the local fire department. This plan shall note the location of all crib infants.
f. A fire drill shall be conducted every three months. Records of the drills shall be maintained on the premises for three years. The records shall give the date, time, weather condition during the drill, number evacuated, description, and evaluation of the fire drill. A fire drill shall be conducted within twentyfour hours of the arrival of each new foster child. Fire drills shall include complete evacuation of all persons from the building.
g. All resident bedrooms shall have emergency egress openings per the SBC.
h. Foster homes with four or more infants shall comply with the requirements of 718300. 11.B., Facilities with Infant Care.
G. ShortTerm Rental Units
1. This regulation shall apply to all shortterm rental units (rental units on a daily or weekly basis). Nothing herein shall apply to condominiums or individually owned residential units which are not used as defined in shortterm rental. Every room, open to the public, that is located in any building used for shortterm rental shall contain a notice as listed in (a), (b), and (c) below. The information shall be legibly printed on a placard or decal 8 1/2 "' in size, prominently affixed on the inside of every exit door in the buildings described above. When affixed, the notices shall not be obstructed by curtains, shades, or other materials.
a. Safety Tips
i. Never smoke in bed;
ii. Locate exits on this floor;
iii. Count the number of doors to the nearest exit;
iv. Check windows to see if and how they open;
v. Keep room key on table next to bed, or when applicable, always keep your key in the same location; and
vi. If you leave your room (or apartment when applicable), keep door closed and take your key.
b. In case of fire
i. Don't panic; remain calm;
ii. Report fire to front desk (or manager or fire department if appropriate);
iii. If room is smokey, get on hands and knees (or stomach) and crawl to the door;
iv. Feel door knob; if hot, do not open door. If door is cool, open slowly;
v. If hallway is smokey, stay next to wall and crawl to exit;
vi. Do not use elevator;
vii. Do not prop doors to exit staircase open; and
viii. Hang on to handrail and walk down the exit staircase. If heavy smoke is encountered, turn around and walk up to roof. Don't let go of handrail.
c. If you cannot leave this room
i. Call front desk (or manager if appropriate) and let them know where you are;
ii. Wet sheets and towels and stuff them in all cracks around doors and vents;
iii. If available, turn on bathroom fan;
iv. Check to see if smoke is outside window; if no smoke, open window;
v. Fill bathtub with cold water for fire fighting;
vi. Using ice bucket, keep doors and walls wet;
vii. Fold a wet towel in a triangle and tie over your nose and mouth; stay low;
viii. If possible, hang a sheet out your window and make yourself visible to rescue personnel. Don't jump; and
ix. Keep fighting fire until help arrives. Don't give up.
2. In addition to the notices placed on the inside of exit doors in the shortterm rental unit, a notice shall be affixed or placed on the counter or other prominent location of the rental office of all shortterm rental units. The notice shall be legibly printed in a minimum of fortyeight point type and shall not be obstructed. The following information, as applicable to the building, shall be printed on the notice.
a. For your safety, this building has the following:
i. automatic sprinkler protection in every room;
ii. automatic sprinkler protection in every hallway;
iii. automatic smoke detectors in every room;
iv. automatic smoke detectors in every hallway;
v. fire extinguishers on every floor;
vi. fire alarm pull stations at every exit;
vii. posted evacuation plans in every room;
viii. pressurized staircase with selfclosing doors. (NOTE: In case of fire, do not prop doors open.);
ix. fire safe staircase with selfclosing doors. (NOTE: In case of fire, do not prop doors open.);
x. emergency lighting and exit lights; and
xi. fire resistant draperies and bedding.
71 8300.12. Alternate Materials and Alternate Methods of Construction.
A. The provisions of these regulations are not intended to prevent the use of any material or method of construction not specifically prescribed by the fire prevention and life safety standards of these regulations. The State Fire Marshal has the authority to approve alternative methods of compliance within the intent of these regulations, after finding that the materials and method of work offered is for the purpose intended, at least the equivalent of that prescribed in these regulations in quality, strength, effectiveness, fire resistance, durability, and safety. The State Fire Marshal shall require sufficient evidence or proof be submitted to substantiate any claim that may be made regarding use of alternative materials and methods.
B. Compliance with NFPA 101, 1997 edition, may be used for consideration of alternative methods if found suitable by the State Fire Marshal.
71 8300.13
Reserved for future use.
71 8300.14
Reserved for future use.
71 8300.15. Statutes, Provisions of Other Codes, and Ordinances.
No provision of this subarticle shall apply to the extent that it is in conflict with any statute of this State, any provision of any building or other code duly adopted by ordinance of a municipality, or any duly adopted ordinance of any municipality. In the event of a conflict, such statute, other provision, or ordinance shall apply in all respects.
71 8301. Use of Hazardous Substances.
71 8301.1. Purpose.
These regulations are for the purpose of safeguarding, to a reasonable degree, life and property from the hazards of fire and explosion arising from the storage, handling, and use of hazardous substances, materials, and devices, and from conditions hazardous to life or property in the use of buildings, structures, or premises.
71 8301.2. Scope.
These regulations shall specifically govern the following: automobile tire rebuilding plants; automobile wrecking yards; junk yards and waste material handling plants; bowling establishments; cellulose nitrate motion picture film; cellulose nitrate plastics (pyrolylin); combustible fibers; compressed gasses; dry cleaning plants; prevention of dust explosions; maintenance of exit ways; explosives, ammunition, and blasting agents; fire protection equipment; application of flammable finishes; flammable and combustible liquids; fruit ripening processes; fumigation and thermal insecticidal fogging; garages; hazardous chemicals; lumber yards and woodworking plants; magnesium; oil burning equipment; manufacture of organic coatings; ovens and furnaces; places of assembly; general precautions against fire; tents; welding or cutting; acetylene generators; and calcium carbide.
71 8301.3. Standard Fire Prevention Code.
A. The provisions of the 1997 edition of the Standard Fire Prevention Code shall constitute the minimum general standard covering the protection of life and property from the hazards of fire and explosion due to storage, use, and handling of hazardous materials, substances and devices, and to provide for minimum hazards to life and property due to panic, exclusive of those hazards considered in building code regulations, provided that the following chapters and sections are hereby deleted and do not constitute a part of the code which is adopted by reference herein.
CHAPTER 1ADMINISTRATION;
CHAPTER 4PERMITS AND CERTIFICATES;
Section 801.3 & 810.1;
CHAPTER 9FLAMMABLE AND COMBUSTIBLE LIQUIDS;
CHAPTER 17LIQUEFIED PETROLEUM GAS;
CHAPTER 19EXPLOSIVES, BLASTING AGENTS, AMMUNITION;
CHAPTER 20FIREWORKS; and
CHAPTER 43FURNISHINGS.
B. All references to the SFPC found in these regulations refer to the edition adopted above.
71 8301.4. Prior Regulations.
Prior regulations pertaining to the contents of these regulations are hereby canceled and suspended; however, Regulation 718301.3 is intended to be in addition to and complementary with Regulation 718300.8.
71 8301.5. Statutes, Provisions of Other Codes, and Ordinances.
No provision of this subarticle shall apply to the extent that it is in conflict with any statute of this State, any provision of any building or other code duly adopted by ordinance of a municipality, or any duly adopted ordinance of any municipality. In the event of such a conflict, such statute, other provision, or ordinance shall apply in all respects.
71 8301.6. Flammable and Combustible Liquids.
The provisions and definitions contained in the NFPA 30, 1996 edition "Flammable and Combustible Liquids Code" shall constitute the minimum general standard covering the protection of life and property from the storage, handling, and use of flammable and combustible liquids. All appendices and referenced publications listed in NFPA 30, 1996 edition, are hereby adopted by reference.
71 8302. Explosives.
(Statutory Authority: South Carolina Explosives Control Act Section 8, 1976 CodeSection 233680, as amended)
A. The provisions contained in NFPA 495 entitled Explosive materials code, 2001 edition, including appendices A, B, C, and D.2 and D.3, shall constitute the minimum standard for the manufacture, transportation, use and storage for all explosives in South Carolina, except as modified herein.
71 8302.1. Definitions.
A. Words not defined in this section shall have the meaning stated in the referenced standard adopted by this regulation.
1. "Ammonium nitrate" means the ammonium salt of nitric acid represented by the formula NH4 NO3.
2. "Authorized, approved, or approval" means authorized, approved, or approval by the South Carolina State Fire Marshal.
3. "AHJ" means Authority Having Jurisdiction which is the State Fire Marshal or his appointed agents.
4. "Issuing authority" means the Office of the South Carolina State Fire Marshal.
71 8302.2. Exceptions.
The following code sections in NFPA 495 are not adopted in South Carolina:
Section 1.1.3
Section 4.1.8
Section 4.6.3
Section 4.7.1 note (2)
Section 7.3.5 Exception 2
Appendix A section A.1.4
This regulation does not apply to the sale or storage of fireworks as regulated by the Department of LLR, Board of Pyrotechnic Safety.
71 8302.3. Licenses and Permits for the Sale, Storage, and Use of Explosive Materials.
A. Licenses
Licenses and permits shall be obtained from the State Fire Marshal as based upon the requirements in Section 233640 of SC Code of Laws and NFPA 495 Table 4.3.2
B. Restrictions.
The following are restrictions that apply to all licenses:
1. No license shall be assigned or transferred;
2. Licenses shall be classified, dated, numbered, and be valid for two years from date of issue;
3. A blaster's license shall bear name, address, photograph, and any other identifying information as deemed necessary by the State Fire Marshal;
4. Criminal background checks shall be conducted on all blaster license applicants. All checks shall be conducted at the expense of the applicant for licensure.
C. Blasting Permits.
1. Permits for blasting shall include the following information:
a. site of blasting;
b. name and license number of blaster;
c. amount and type of explosive materials;
d. proximity of gas lines, power transmission lines, public roads, and waterways;
e. purpose of blasting: and
f. corporate name, if any.
D. Magazine Permits.
1. The permit form shall contain the following information regarding the exact physical location:
a. town and county;
b. street address;
c. location from other magazines and buildings;
d. owner's name;
e. quantity of explosives being stored;
f. license number (dealer or blaster): and
g. type of explosive materials.
2. Prior to use, each magazine shall be inspected and approved by personnel of the Office of State Fire Marshal.
3. All magazines shall be placarded on all four sides. Placards shall be a minimum of 8 inches in height, and letters of at least 3 inches in height.
4. Giving false information or making a misrepresentation to obtain a license or permit.
E. The State Fire Marshal may suspend a license or permit pending disposition of a felony charge brought against a licensee or permittee which involves the use of explosives. The State Fire Marshal may accept a relief from disability incurred by reason of a criminal conviction of any crime punishable by a term of imprisonment exceeding two years that has been granted by the Director of the Bureau of Alcohol, Tobacco and Firearms, United States Department of the Treasury, Washington, D.C., pursuant to Section 55.142, Subpart H, Title 27, Code of Federal Regulations and Title 18 United States Code, Chapter 40, Section 845(b).
71 8302.4. [Reserved]
71 8302.5. [Reserved]
71 8302.6. [Reserved]
71 8302.7. [Reserved]
71 8302.8. [Reserved]
71 8302.9. [Reserved]
71 8302.10. Records.
A. Each licensed blaster shall keep records of each blast. All records including seismograph reports shall be retained for at least five years and shall be available for inspection by the Office of State Fire Marshal and shall contain the following minimum data:
1. name of company or contractor;
2. location, date, and time of blast;
3. name, signature, and license number of blaster in charge;
4. type of material blasted;
5. number of holes, burden and spacing;
6. diameter and depth of holes;
7. types of explosives used;
8. total amount of explosives used;
9. maximum amount of explosives per delay period of 8 milliseconds or greater;
10. method of firing and type of circuit;
11. direction and distance in feet to nearest dwelling house, public building, school, church, commercial or institutional building neither owned nor leased by the person conducting the blasting;
12. weather conditions;
13. type and height or length of stemming;
14. whether mats or other protections were used;
15. type of delay electric blasting caps used and delay periods used;
16. exact location of seismograph, if used, and the distance of seismograph from blast as indicated accurately by the person taking the seismograph reading;
17. seismograph records, where required including:
a. name of person and firm analyzing the seismograph record: and
b. seismograph reading
18. maximum number of holes per delay period of eight milliseconds or greater: and
19. blaster's report if deemed necessary by Office of State Fire Marshal. This report will be completed on forms provided by the Office and submitted within three working days of the blast.
71 8302.11. Blasting Safety.
A. This section sets forth additional requirements to supplement NFPA 495 and provide for safe blasting operations.
1. If, as a result of a blast, the vibrational levels are exceeded or material is hurled through the air causing damage to homes or other property, or causing personal injury or death, or endangering public safety, health and general welfare, in violation of these regulations, the Office of State Fire Marshal may consider this due cause for revocation of blaster's license and assess penalties.
2. The contractor or operator, as well as the blaster, shall be responsible for the conduct of blasting on any operation.
3. These regulations are in no way intended to relieve the contractor or operator or other persons of responsibility and liability under any other laws.
4. The State Fire Marshal may require a seismograph be used on any blasting operation in which he feels that damage to personal property has or may occur.
5. A seismograph shall be used on all blasting operations that occur within 1500 feet of an inhabited structure, and in every instance where the scaled distances shown in NFPA 495 are not followed with the written approval of the State Fire Marshal.
71 8302.12. [Reserved]
71 8302.13. [Reserved]
71 8302.14. [Reserved]
71 8302.15. [Reserved]
71 8302.16. [Reserved]
71 8302.17. [Reserved]
71 8302.18. Firing the Blast.
A. This section sets forth additional requirements for firing the blast.
1. A warning signal shall be given before every blast. Warning signals shall comply with the following:
a. Warning signal is a 1 minute series of long horn or siren blasts 5 minutes prior to the blast signal.
b. Blast signal is a series of short horn or siren blasts 1 minute prior to the shot.
c. All clear signal is a prolonged horn or siren blast following the inspection of the blast area.
2. Before a blast is fired, a loud warning signal shall be given by the licensed blaster in charge, who has made certain that all surplus explosives have been returned to the magazine, and all employees, vehicles, and equipment are at a safe distance or under sufficient cover.
71 8302.19. [Reserved]
71 8302.20. [Reserved]
71 8302.21. [Reserved]
71 8302.22. [Reserved]
71 8302.23. [Reserved]
71 8302.24. Explosives Investigations.
A. All costs incurred by the State Fire Marshal for investigations involving explosives or blasting operations shall be reimbursed to the State by the individual or company involved in the investigation. Such reimbursements will only apply when the individual or company has been found in violation of the State Explosives Control Act or these Regulations.
71 8302.25. Variances.
A. This section provides licensees and permittees the opportunity to request variances of the promulgated regulations under specific conditions.
1. The State Fire Marshal may grant variances if it can be demonstrated the variance improves safety conditions or that the variance will provide such safe conditions as those which would prevail if there was compliance with the standard.
2. Such a variance may be modified or revoked by the State Fire Marshal.
71 8303. Service Stations.
71 8303.1. National Fire Protection Association Pamphlets No. 30 and 30A.
The applicable provisions and definitions contained in the NFPA 30, 1996 edition and 30A, 1996 edition, shall constitute the minimum general standards for the protection of life and property from the hazards of storing, handling, and use of flammable and combustible liquids at service stations. All referenced publications listed in NFPA 30 and 30A are hereby adopted by reference.
Exception 1: Unattended selfservice stations as addressed in Section 95.2 of NFPA 30A, 1996 edition, shall only be allowed where key and card lock type dispensing devices are used.
Exception 2: Automatic fueling clips shall be allowed.
Exception 3: The aboveground storage of flammable and combustible liquids shall comply with South Carolina Code (1976 as amended) Section 3941260.
71 8304. Liquefied Petroleum Gas Board.
71 8304.1. National Fire Protection Association Pamphlet No. 58.
The applicable provisions and definitions contained in the NFPA Pamphlet No. 58, 1998, edition, and all referenced pamphlets therein, as provided by Section 394330, shall constitute the minimal general standards covering the design, construction, location, installation and operation of equipment for storing, handling, transporting by tank truck or tank trailer, and utilizing liquefied petroleum gases and the odorization of such gases and the degree thereof.
71 8305. Transportation and Use of Pyrotechnics.
71 8305.1. General.
A. The purpose of this regulation is to provide reasonable safety and protection to the general public, display operator, and public and private property when viewing a public fireworks display. (See definition of "public display.")
B. This regulation shall apply to the construction for shells and mortars, handling, use and transportation of fireworks intended solely for public display. It shall also apply to the general conduct and operation of the display.
C. This regulation shall not apply to the manufacture, sale, or storage of fireworks.
D. This regulation shall not apply to the transportation, handling, and/or use of fireworks by the Armed Forces of the United States, law enforcement officials and/or the State Fire Marshal or his designated representative, provided that they are acting within their respective official capacities in emergency situations that present a clear and present danger to public safety.
E. This regulation shall not apply to the transportation, handling, or use of industrial pyrotechnic devices or fireworks, such as railroad torpedoes, fuses, and automotive, aeronautical, and marine flares and smoke signals.
71 8305.2. Definitions.
A. For the purpose of these regulations, the following terms shall mean:
1. "Authority Having Jurisdiction" means the Office of the State Fire Marshal or the fire department supplying fire suppression equipment and personnel of the municipality or county where a display is to take place.
2. "Black Match" means a fuse made from thread impregnated with black powder and used for igniting pyrotechnic devices.
3. "Boxed Finale" means a number of mortars grouped closely together and contained by a suitable frame. The mortars are loaded prior to the display and fused for rapid sequence firing.
4. "Break" means an individual effect from an aerial shell; generally either color (stars) or noise (salute). Aerial shells can be singlebreak (having only one effect) or multiplebreak (having two or more effects).
5. "Colored Pot" means a paper tube containing pyrotechnic composition that produces a colored flame on ignition. Colored pots are used in the construction of ground display pieces.
6. "Discharge Site" means the area immediately surrounding the mortars used to fire the aerial shells.
7. "Finale Rack" means a row of closely spaced two inch (51 mm) or three inch (76 mm) (inside diameter) mortars held in a wooden frame. It is similar to a boxed finale.
8. "Fireworks" means any composition or device for the purpose of producing a visible or an audible effect by combustion, deflagration, or detonation, and which meets the definition of "common" or "special" fireworks as set forth in the United States Department of Transportation (DOT) Hazardous Materials Regulations, Title 49, Code of Federal Regulations, Parts 173.88 and 173.100.
a. The following are exceptions:
i. toy pistols, toy canes, toy guns, or other devices in which paper and/or plastic caps, manufactured in accordance with United States Department of Transportation regulations, 49 CFR 173.100(p), and packed and shipped according to said regulations, are not considered to be fireworks and shall be allowed to be used and sold at all times;
ii. model rockets and model rocket motors designed, sold, and used for the purpose of propelling recoverable aero models are not considered to be fireworks;
iii. propelling or expelling charges consisting of a mixture of sulfur, charcoal, and saltpeter are not considered as being designed for producing audible effects; and
iv. items designed in 9.d. of the definition of "Common Fireworks."
9. "Common Fireworks" means any small firework device designed primarily to produce visible effects by combustion and which must comply with the construction, chemical composition and labeling regulations of the United States Consumer Products Safety Commission, as set forth in Title 16, Code of Federal Regulations, Part 1507. Some small devices designed to produce audible effects are included, such as whistling devices, ground devices containing 50 milligrams or less of explosive composition, and aerial devices containing 130 thirty milligrams or less of explosive composition. Common fireworks are classified as Class C explosives by the United States Department of Transportation and include the following:
a. Ground and Handheld Sparkling Devices.
i. "Dipped Stick; Sparkler" means stick or wire coated with pyrotechnic composition that produces a shower of sparks upon ignition. Total pyrotechnic composition may not exceed 100 grams per item. Those devices containing any perchlorate or chlorate salts may not exceed 5 grams of pyrotechnic composition per item. Wire sparklers which contain no magnesium and which contain less than 100 grams of composition per item are not included in this category, in accordance with United States Department of Transportation regulations.
ii. "Cylindrical Fountain" means cylindrical tube not more than 3/4 inches (19 mm) inside diameter, containing up to seventyfive grams of pyrotechnic composition. Upon ignition, a shower of colored sparks, and sometimes a whistling effect, is produced. This device may be provided with a spike for insertion into the ground (spike fountain), a wood or plastic base for placing on the ground (base fountain), or a wood or cardboard handle, if intended to be handheld (handle fountain).
iii. "Cone Fountain" means cardboard or heavy paper cone containing up to 50 grams of pyrotechnic composition. The effect is the same as that of a cylindrical fountain.
iv. "Illuminating Torch" means cylindrical tube containing up to 100 grams of pyrotechnic composition. Upon ignition, colored fire is produced; may be spike, base, or handheld.
v. "Wheel" means pyrotechnic device attached to a post or tree by means of a nail or string. Each wheel may contain up to 6 "driver" units: tubes not exceeding 1/2 inch (12.5 mm) inside diameter and containing up to 60 grams of pyrotechnic composition. Upon ignition, the wheel revolves, producing a shower of color and sparks and, sometimes, a whistling effect.
vi. "Ground Spinner" means small device similar to a wheel in design and effect and placed on the ground and ignited. A shower of sparks and color is produced by the rapidly spinning device.
vii. "Flitter Sparkler" means narrow paper tube filled with pyrotechnic composition that produces color and sparks upon ignition. This device does not have a fuse for ignition. The paper at one end of the tube is ignited to make the device function.
b. Aerial Devices.
i. "Sky Rocket" means tube not exceeding 1/2 inch (12.5 mm) inside diameter that may contain up to twenty grams of pyrotechnic composition. Sky rockets contain a wooden stick for guidance and stability and rise into the air upon ignition. A burst of color, noise, or both is produced at the height of flight.
ii. "Missiletype Rocket" means a device similar to a sky rocket in size, composition, and effect that uses fins rather than a stick for guidance and stability.
iii. "Helicopter, Aerial Spinner" means a tube not more than 1/2 inch (12.5 mm) inside diameter and containing up to 20 grams of pyrotechnic composition. A propeller or blade is attached which, upon ignition, lifts the rapidly spinning device into the air. A visible or audible effect is produced at the height of flight.
iv. "Roman Candle" means heavy paper or cardboard tube not exceeding 3/8 inch (9.5 mm) inside diameter and containing up to 20 grams of pyrotechnic composition. Upon ignition, up to 10 "stars" (pellets of pressed pyrotechnic composition that burn with bright color) are individually expelled at several second intervals.
v. "Mine Shell" means heavy cardboard or paper tube up to 2 1/2 inches (63.5 mm) inside diameter attached to a wood or plastic base and containing up to 40 grams of pyrotechnic composition. Upon ignition, "stars," firecrackers, or other devices are propelled into the air. The tube remains on the ground.
c. Audible Ground Devices.
i. "Firecracker, Salute" means small paperwrapped or cardboard tube containing not more than 50 milligrams of pyrotechnic composition. Upon ignition, noise and a flash of light are produced.
ii. "Chaser" means small paper or cardboard tube that travels along the ground upon ignition. A whistling effect, or other noise, is often produced. The explosive composition used to create the noise may not exceed 50 milligrams.
iii. "Combination Items" means fireworks devices containing combinations of two or more of the effects described in Categories 1, 2, and 3.
d. Novelties.
Items listed in this section are not classified as common fireworks by the United States Department of Transportation.
i. "Snake, Glow Worm" means pressed pellet of pyrotechnic composition that produces a large, snakelike ash upon burning. The ash expands in length as the pellet burns. These devices may not contain mercuric thiocyanate.
ii. "Smoke Device" means tube or sphere containing pyrotechnic composition that, upon ignition, produces white or colored smoke as the primary effect.
iii. "Wire Sparkler" means wire coated with pyrotechnic composition that produces a shower of sparks upon ignition. These items may not contain magnesium and must not exceed 100 grams of composition per item. Devices containing any chlorate or perchlorate salts may not exceed 5 grams of composition per item.
e. "Trick Noisemaker" means an item that produces a small report intended to surprise the user. These devices include:
i. "Party Popper" means small plastic or paper item containing not more than 16 milligrams of explosive composition that is friction sensitive. A string protruding from the device is pulled to ignite it expelling paper streams and producing a small report.
ii. "Booby Trap" means small tube with string protruding from both ends, similar to a party popper in design. The ends of the string are pulled to ignite the friction sensitive composition, producing a small report.
iii. "Snapper" means small, paper wrapped item containing a minute quantity of explosive composition coated on small bits of sand. When dropped, the device explodes producing a small report.
iv. "Trick Match" means kitchen or book match that has been coated with a small quantity of explosive or pyrotechnic composition. Upon ignition of the match, a small report or a shower of sparks is produced.
v. "Auto Burglar Alarm" means tube which contains pyrotechnic composition that produces a loud whistle and/or smoke when ignited. A small quantity of explosive, not exceeding 50 milligrams, may also be used to produce a small report. A squib is used to ignite the device.
10. "Special Fireworks" means large fireworks designed primarily to produce visible or audible effects by combustion, deflagration, or detonation. This term includes, but is not limited to, firecrackers containing more than 2 grains (130 mg) of explosive composition, aerial shells containing more than 40 grams of pyrotechnic composition, and other display pieces which exceed the limits for classification as "Common Fireworks."
11. "Ground Display Piece" means a pyrotechnic device that functions on the ground (as opposed to an aerial shell which functions in the air). Typical ground display pieces include fountains, roman candles, wheels, and "set pieces."
12. "Labeled" means having a label, symbol or other identifying mark of an organization concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials and by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
13. "Lance" means a thin cardboard tube packed with colorproducing pyrotechnic composition used to construct ground display pieces. Lances are mounted on a wooden frame and fused so that ignition of all tubes is simultaneous.
14. "Lift Charge" means that part of an aerial shell which actually lifts the shell into the air. It usually consists of a black powder charge ignited by a quick match fuse. (A delay fuse then ignites the main part of the shell, producing the desired effect.)
15. "Listed" means equipment or materials acceptable to the "authority having jurisdiction" and included in a list published by an organization concerned with product evaluation that maintains periodic inspection of production of listed equipment or materials and whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner. Note: The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of which do not recognize equipment as listed unless it is also labeled. The "authority having jurisdiction" should utilize the system employed by the listing organization to identify a product.
16. "Monitor" means a person designated by the sponsors of the display to keep the audience in the intended viewing area and out of the discharge site and potential landing area.
17. "Mortar" means a metal or heavy cardboard tube from which aerial shells are fired.
18. "Movable Ground Piece" means a ground display piece having movable parts, such as a revolving wheel.
19. "Operator" means the person responsible for setting up and firing a public fireworks display.
20. "Potential Landing Area" means the area over which aerial shells are fired. Debris and malfunctions may fall into this area; therefore, it must be kept clear of spectators.
21. "Public Display" means an outdoor display of aerial pyrotechnic shells and/or ground display pieces.
22. "Quick Match" means black match that is encased in a loose fitting paper sheath. While exposed black match burns slowly, quick match propagates flame extremely rapidly, almost instantaneously. Quick match is used in fuses for aerial shells and for simultaneous ignition of a number of pyrotechnic devices, such as lances in a ground display piece.
23. "Safety Cap" means a paper tube, closed at one end, that is placed over the end of an aerial shell to protect it from accidental ignition. The cap is not removed until just before firing of the shell.
24. "Shell or Aerial" means a cylindrical or spherical cartridge containing pyrotechnic composition, a long fuse, and a black powder lift charge. The shells are most commonly 3 inches (76 mm) to 6 inches (152 mm) outside diameter and are fired from mortars. Upon firing, the fuse and lift charge are consumed.
71 8305.3. Qualifications of Display Operators.
A. The person in actual charge of the firing of the fireworks in a display shall be competent for the task and so certified by the State Fire Marshal. The operator shall have his Certificate of Competency in his possession when engaged in conducting a display and shall exhibit his certificate on request of any authorized official. An applicant must meet all of the following requirements before receiving a certificate:
1. Applicant must be at least twentyone years of age;
2. Applicant shall furnish a notarized statement concerning his participation in at least 6 fireworks displays and indicating for each display the date, the site, and the name and certificate number of the supervising operator.
3. Applicant must successfully complete the written examination administered by the State Fire Marshal.
4. Any applicant who fails the written examination shall be afforded the opportunity to be retested, once only, after a 7 day waiting period; and
5. Any applicant who fails the retest shall be required to wait at least six months before he can reapply.
B. Each person assisting the Certified Operator and engaged in the firing of the fireworks shall be at least twentyone years of age.
C. The certification of any operator who violates the regulations on laws of the State may be revoked or suspended by the State Fire Marshal.
D. Each Certified Operator shall be required to attend a recertification class and successfully complete a written examination provided by the State Fire Marshal every two years.
71 8305.4. Permits and General Requirements for Fireworks Displays.
A. Any person who desires to hold a fireworks display shall first obtain a permit form from the supplier of the fireworks. Permit forms are furnished by the State Fire Marshal. The permit form shall be signed by the Resident Fire Marshal or Fire Chief of the department providing fire suppression equipment and personnel of the municipality or county where such display is to take place.
B. Public liability insurance set at a minimum limit of $500,000 shall be furnished by the fireworks supplier to include the display sponsor as an additional insured. Coverage company shall be licensed to conduct business in South Carolina.
C. Upon validation of the permit form by the Resident Fire Marshal or Fire Chief of the department providing fire suppression equipment and personnel of the municipality or county where such display is to take place, the sponsor of the display shall forward all five copies to the State Fire Marshal along with a copy of the insurance policy and a detailed diagram of the display site fifteen working days prior to the display. Validation permit shall be cosigned by the State Fire Marshal or his agent.
D. When approved by the State Fire Marshal, the permit copies will be distributed as follows:
1. The State Fire Marshal shall retain the original along with the insurance certificate and diagram;
2. The second copy shall be returned to the sponsor;
3. The third copy shall be forwarded to the supplier, which will authorize shipment of the fireworks; and
4. The fourth copy shall be sent to the Board of Pyrotechnic Safety.
E. All display material shall be purchased through a pyrotechnic manufacturer or distributor licensed to do business in the State by the Board of Pyrotechnic Safety, and the firing of the display shall be done by an operator certified as competent for this task by the State Fire Marshal.
F. If a display is postponed due to any circumstances, the sponsor of the display shall notify the authority having jurisdiction of the alternate date before presenting the display.
G. The person or organization applying for a permit shall be responsible for arranging the detailing of at least two members of the local fire department, along with necessary equipment, or such other larger number as may be deemed necessary by the authority having jurisdiction to be on the display site during the firing of the fireworks. Fire department personnel shall remain until the termination of the display and all fireworks and debris have been removed from the site.
H. If onduty fire personnel are not available, it shall be the responsibility of the permittee to arrange with the authority having jurisdiction for the detailing of offduty firemen and equipment and to compensate the firemen for the time involved.
I. The permit shall require such information issued on forms as:
1. organization sponsoring display;
2. company name supplying fireworks;
3. display operator's name;
4. date of display;
5. time of display;
6. fire department present during display;
7. fire chief's name;
8. time and date display site will be ready for final inspection by authorities;
9. diagram of display site and directions to same; and
10. copy of insurance policy.
71 8305.5. Requirements for Shells and Mortars for Public Displays.
A. Shells shall be classified and described only in terms of the inside diameter of the mortar in which they can be safely used (e.g., 3 inch (76 mm) shells are only for use in three inch (76 mm) mortars).
B. Shells shall be constructed so that the difference between the inside diameter of the mortar and the outside diameter of the shell is no less than 1/8 inch (3.2 mm) and no more than 1/4 inch (6.4 mm) for twoinch (51 mm) and threeinch (76 mm) shells or 1/2 inch (12.7 mm) for shells larger than 3 inches (76 mm).
C. Shells shall be labeled with the type of shell, the diameter measurement, and the name of the manufacturer or distributor. Shells shall also carry a warning label.
D. The length of the internal delay fuse and the amount of lift charge shall be sized to ensure proper functioning of the shells in their mortars. Quick match fuse shall be long enough to allow not less than 6 inches (152 mm) of fuse to protrude from the mortar after the shell has been properly inserted.
E. The length of exposed black match on a shell shall not be less than 3 inches (76 mm), and the fuse shall not be folded or doubled back under the safety cap. Also, the time delay between ignition of the tip of the exposed black match and ignition of the lift charge shall not be less than 4 seconds to allow the operator to retreat safely.
F. A safety cap shall be installed over the exposed end of the fuse. The safety cap shall be of a different color than that used for the paper of the fuse.
G. After the fireworks have been delivered to the display site, they shall not be left unattended nor shall they be allowed to become wet.
H. All shells shall be inspected upon delivery to the display site by the display operator. Any shells having tears, leaks, broken fuses, or showing signs of having been wet shall be set aside and shall not be fired. After the display, any such shells shall either be returned to the supplier or be destroyed according to the supplier's instructions.
I. All shells shall be separated according to diameter and stored in tightly covered containers of metal, wood, or plastic or in fiber drums or corrugated cardboard cartons meeting United States Department of Transportation specifications for transportation of fireworks. A flameresistant tarpaulin meeting the requirements of NFPA 701, Standard Methods of Fire Tests for FlameResistant Textiles and Films, shall be permitted to be used as a covering over the containers, if additional protection is desired.
J. The shell storage area shall be located at a distance of not less than 20 feet (6 m) from the discharge site. Exception: Where acceptable to the authority having jurisdiction, alternate protective measures may be used.
K. During the display, shells shall be stored upwind from the discharge site. If the wind should shift during the display, the shell storage area shall be relocated so as again to be upwind from the discharge site. Where conditions do not permit locating the shell storage area upwind from the discharge site, a flameresistant tarpaulin meeting NFPA 701 requirements shall be used to cover the shell storage.
L. Mortars shall be inspected for dents, bent ends, and cracked or broken plugs prior to ground placement. Mortars found to be defective in any way shall not be used. Any scale on the inside surface of the mortars shall be removed.
M. Mortars shall be positioned so that the shells are carried away from spectators and into a clear area acceptable to the authority having jurisdiction.
N. Mortars shall be either buried securely into the ground to a depth of 2/3 to 3/4 of their length or fastened securely in mortar boxes or drums. In soft ground, heavy timber (e.g., 4 inches (102 mm) thick) or rock slabs shall be placed beneath the mortars to prevent their sinking or being driven into the ground during firing. Boxed finales and finale racks shall not be required to be buried; however, they shall be sufficiently supported and braced to ensure stability during firing.
O. In damp ground, a weather resistant bag shall be placed under the bottom of the mortar prior to placement in the ground to protect the mortar against moisture.
P. Weather resistant bags shall be placed over the open end of the mortar in damp weather to keep moisture from accumulating on the inside surface of the mortar.
Q. Sand bags, dirt boxes, or other suitable protection shall be placed around the mortars to protect the operator from ground bursts. This requirement shall not apply to the down range side of the discharge site.
R. Mortars shall be inspected before the first shells are loaded to be certain that no water or debris has accumulated in the bottom of the mortar.
S. Metal mortars shall be deemed acceptable for use with all shells. Paper mortars shall only be used for discharge of single and double break shells. A thirtysecond cooling period shall be allowed between firing and reloading of paper mortars.
T. Paper mortars shall be constructed of convolute wound paper, except that spiral wound paper shall be permitted for threeinch (76 mm) diameter mortars only. Wall thickness of paper mortars shall conform to Table I.
TABLE I
WALL THICKNESS OF PAPER MORTARS
Mortar Diameter Wall Thickness
Mortar Type in. (mm) in. (mm)
Convolute 2 in. (51) 1/4 in. (6.4)
Convolute or Spiral 3 in. (76) 3/8 in. (9.6)
Convolute 4 in. (102) 1/2 in. (12.7)
Convolute 5 in. (127) 3/4 in. (19.0)
Convolute 6 in. (152) 3/4 in. (19.0)
Exception: For threeinch (76 mm) single fire mortars, such as used in finales, a wall thickness of 1/4 inch (6.4 mm) shall be permitted.
U. A cleaning tool shall be provided for cleaning debris out of the mortars between firings.
V. All mortars of the same inside diameter shall be grouped together to minimize the possibility of shells being placed in the wrong size mortars. Mortars shall be spaced apart by at least twice their inside diameters.
71 8305.6. Requirements for Site Selection for Display.
A. The intent of this section is to provide minimum clearances upon which the authority having jurisdiction may base approval of the display site. Where unusual conditions exist, the authority having jurisdiction may increase the minimum clearances as necessary.
B. The areas selected for the discharge site, spectator viewing area, parking areas, and the potential landing area shall be inspected and approved by the authority having jurisdiction.
C. The area selected for the discharge of aerial shells shall be located so that the trajectory of the shells will not come within 50 ft. (15.2 m) of any overhead object.
D. Ground display pieces shall be located at a minimum distance of 150 ft. (45.6 m) from spectator viewing areas and parking areas.
E. Mortars shall be separated from spectator viewing areas and parking areas, from health care and penal facilities, from storage of hazardous materials, and from residential occupancies by the minimum distances specified in Table II.
TABLE II
MORTAR SEPARATION DISTANCES
Spectator Viewing Area Health Care & Storage of Clear
Parking Area 1 & 2 Penal Hazardous Landing
Family Dwellings Facilities Materials Area
Mortar 300 feet 500 feet 500 feet 300 feet
Firing (91.4 m) (132.4 m) (132.4 m) (91.4 m)
Site
F. Fireworks shall not be discharged within 300 feet (91.4 m) of any tent or canvas shelter.
G. The potential landing area shall be a large, clear, open area acceptable to the authority having jurisdiction.
H. Spectators, vehicles, or any readily combustible materials shall not be located within the potential landing area during the display.
I. The potential landing area shall be located according to the distances specified in Table II and shall also comply with the requirements of Section F above.
71 8305.7. Requirements for Operation of the Display.
A. Certified operators and assistants shall not smoke, consume alcoholic beverages, or be under the influence of narcotics or drugs while handling and/or firing fireworks during a display.
B. Monitors, whose sole duty shall be the enforcement of crowd control, shall be located around the display area by the sponsor. The authority having jurisdiction shall determine the number of monitors needed and their placement.
C. Monitors shall be located around the discharge site to prevent spectators or any other unauthorized persons from entering the discharge site. The discharge site shall be so restricted throughout the display and until the discharge site has been inspected after the display. Where practical, fences and rope barriers shall be used to aid in crowd control.
D. If, in the opinion of the authority having jurisdiction or the display operator, lack of crowd control should pose a danger, the display shall be immediately discontinued until such time as the situation is corrected.
E. If, at any time, high winds or unusually wet weather prevail, such that in the opinion of either the authority having jurisdiction or the display operator a definite danger exists, the public display shall be postponed until weather conditions improve to an acceptable level.
F. Light snow or mist need not cause cancellation of the display; however, all materials used in the display shall be protected from the weather by suitable means until immediately prior to use.
G. Display operators and assistants shall use only flashlights or electric lighting for artificial illumination.
H. No smoking or open flames shall be allowed within 50 feet of the shell storage area as long as shells are present. Signs to this effect shall be conspicuously posted.
I. Shells shall be carried from the storage area to the discharge site only by their bodies, never by their fuses. Exception: As specified in Section K below.
J. Shells shall be checked for proper fit in their mortars prior to the display.
K. When loaded into the mortars, shells shall be held by the thick portion of their fuses and carefully lowered into the mortar. At no time shall the operator place any part of his body over the throat of the mortar.
L. The operator shall be certain that the shell is properly seated in the mortar.
M. Shells shall not, under any circumstances, be forced into a mortar too small to accept them. Shells that do not fit properly into the mortars shall not be fired; they shall be disposed of according to the procedure described in Section R below.
N. Shells shall be ignited by lighting the tip of the fuse with a fusee, torch, portfire, or similar device. The operator shall never place any part of his body over the mortar at any time. As soon as the fuse is ignited, the operator shall retreat from the mortar area. Exception: Alternatively, electrical ignition may be used.
O. The safety cap protecting the fuse shall not be removed by the operator responsible for igniting the fuse until immediately before the shell is to be fired. Exception: Where electrical ignition is used.
P. The first shell fired shall be carefully observed to determine that its trajectory will carry it into the intended firing range and that the shell functions over, and any debris falls into, the potential landing area.
Q. The mortars shall be reangled or reset, if necessary, at any time during the display.
R. In the event of a shell failing to ignite in the mortar, the mortar shall be left alone for a minimum of 5 minutes, then carefully flooded with water. Immediately following the display, the mortar shall be emptied into a bucket of water. The supplier shall be contacted as soon as possible for proper disposal instructions.
S. Operators shall never attempt to repair a damaged shell nor shall they attempt to dismantle a dry shell. In all such cases, the supplier shall be contacted as soon as possible for proper disposal instructions.
T. Operators shall never dry a wet shell, lance, or pot for reuse. In such cases, the shell, lance, or pot shall be handled according to the procedure in Section R above.
U. The entire firing range shall be inspected immediately following the display for the purpose of locating any defective shells. Any shells found shall be immediately doused with water before handling. The shells shall then be placed in a bucket of water. The supplier shall then be contacted as soon as possible for proper disposal instructions.
V. When fireworks are displayed at night, the sponsor shall ensure that the firing range is inspected early the following morning.
W. The operator of the display shall keep a record, on a form provided by the supplier, of all shells that fail to ignite or fail to function. The form shall be completed and returned to the supplier (See 718305.11). Forms will be provided by the State Fire Marshal.
X. All ground pieces shall be positioned out of the firing range of aerial displays. Mortars shall be positioned so that they do not fire towards any ground pieces.
Y. No dry grass or combustible material shall be located beneath ground pieces. If dry, the area shall be thoroughly wet down before the display.
Z. Poles for ground pieces shall be securely placed and firmly braced so that they will not fall over when they function.
AA. Specific instructions from the supplier shall accompany all ground pieces. A list of required accessories shall also be supplied.
71 8305.8. Use of Class "C" Fireworks in South Carolina.
A. It shall be deemed a violation of these regulations to:
1. explode or ignite fireworks within 600 ft. (182.9 m) of any church, hospital, asylum, school, place of assembly, service station, bulk storage plant, or any other facility that stores or dispenses flammable liquids and/or hazardous materials;
2. explode or ignite fireworks within 75 ft. (22.9 m) of where fireworks are stored, sold or offered for sale;
3. ignite, discharge, and/or throw fireworks from any motor vehicle or to place or throw fireworks into or at any motor vehicle;
4. ignite or discharge fireworks in a wanton or reckless manner so as to constitute a threat to the personal safety or property of another.
71 8305.9. Transportation of Pyrotechnics in South Carolina.
A. Vehicles transporting pyrotechnics classified as Class "B" explosives in any quantity and pyrotechnics classified as Class "C" explosives in quantities greater than 1000 lbs. shall be in the custody of drivers who are physically fit, careful, capable, reliable, able to read and write the English language, not addicted to the use or under the influence of intoxicants or narcotics, and not less than eighteen years of age.
B. On both sides, on the front,m and on the rear, vehicles transporting pyrotechnics classified as Class "B" explosives in any quantity and pyrotechnics classified as Class "C" explosives in quantities greater than 1000 lbs. shall prominently display signs marked "EXPLOSIVES" that conform with United States Department of Transportation and other federal regulations.
C. The fire and police departments shall be promptly notified when a vehicle transporting pyrotechnics is involved in an accident, break down, or fire. Only in the event of such an emergency shall the transfer of pyrotechnics from one vehicle to another be allowed on highways and then only when qualified supervision is provided.
D. Any vehicle used for the transportation of pyrotechnics shall be equipped with not less than one approved type fire extinguisher with a minimum rating of 2A 20 BC. Extinguisher shall be so located as to be readily available for use.
71 8305.10. Pyrotechnic Powder in Entertainment and Assembly Occupancies.
Black powder, flash powder, or any other powder composed of pyrotechnic materials is strictly prohibited from use inside any enclosed entertainment and/or assembly occupancy located within the State of South Carolina.
71 8305.11. Forms.
A. Permit to Stage Fireworks Displays.
Permit to Stage Fireworks Display
City___
County__________ Date___
1. Organization sponsoring display___
Address___
Individual representing organization__________ Telephone___
Address___
2. Name of company supplying fireworks___
Address__________ Telephone___
3. Display operator's name__________
Address__________ Telephone___
4. Date of display__________ Date receiving fireworks___
Rain date___
5. Time of display__________ Location___
6. Fire department that will be present during display___
7. Fire chief's name__________ Telephone___
Address___
8. Time and date display site will be ready for final inspection by authorities___
9. Attach a separate sheet showing diagram of display site and directions to same.
10. A copy of insurance policy is to be attached with this permit and sent to:
SC Department of Labor, Licensing & Regulation
Office of State Fire Marshal
141 Monticello Trail
Columbia, SC 29203
____________________
Permittee
Resident Fire Marshal (Fire Chief)
Title
State Fire Marshal or His Designee
B. Malfunctioning Shell Report.
Malfunctioning Shell Report
The following information shall be furnished to the State Fire Marshal no later than fifteen days after the execution of the display by the supplier of fireworks.
Date of Display__________ Location___
Operator___
Type of Shell Involved:
Manufacturer___
Size___
Effect___
Type of Malfunction:
Fuse ignited, but nothing else happened___
Shell exploded in mortar___
Shell exploded just out of mortar___
Shell returned to ground and then exploded___
Shell returned to ground but never exploded___
Other (explain)___
__________
(Signature of Certified Operator)
RETURN FORM PROMPTLY TO SUPPLIER OF FIREWORKS FOR DISPLAY
71 8306. Tents, Grandstands, and AirSupported Structures.
71 8306.1. Tents, Grandstands, and AirSupported Structures Standards.
A. The provisions of the NFPA 102, 1995 edition, Standard for Grandstands, Folding and Telescopic Seating, Tents, and Membrane Structures, as amended, shall constitute the minimum fire prevention and protection standards for the prevention of fire and for the protection of life in tents, folding and telescopic seating, and airsupported structures.
B. The provisions of the SBC shall constitute the minimum fire prevention and protection standards for the prevention of fire and for the protection of life in grandstands.
71 8306.2. Scope, Purpose and Definitions.
A. NFPA 102, 1995 edition, as amended, is concerned with the hazards of fire, storm, collapse, and panic, and covers the construction, location, protection and maintenance of tents and airsupported structures used for assembly; interior folding or telescopic seating normally used in gymnasiums, multiuse rooms, and similar indoor mass seating as differentiated from grandstands and bleachers intended primarily to support persons for purposes of assembly for outdoor use. For the purpose of this standard, certain terms, words, and phrases shall be construed as set forth in Chapter 2 "Definitions," of the standards.
B. The SBC is concerned with the hazards of fire, storm, collapse, and panic, and covers the construction, location, protection and maintenance of reviewing stands, grandstands, and bleachers intended primarily to support persons for purposes of assembly for outdoor use. For the purpose of this section, certain terms, words, and phrases shall be construed as set forth in the SBC.
71 8307. Fire ExtinguishersPortable and Fixed Station.
71 8307.1. Purpose.
The purpose of this subarticle is to regulate the leasing, renting, selling and servicing of portable fire extinguishers, and the installation and servicing of fixed fire extinguishing systems in the interest of protecting lives and property.
71 8307.2. Administration; Filing of Publications; Statutes, Provisions of Other Codes and Ordinances.
A. This subarticle shall be administered by the Office of State Fire Marshal and all Orders requiring corrective action as a result of this subarticle shall be issued by a Deputy State Fire Marshal or Certified Resident State Fire Marshal.
B. No provision of this subarticle shall be held to deprive any governing body having jurisdiction of any power or authority which it had on the effective date of these regulations. However, any governing body having jurisdiction shall not permit lesser requirements than those prescribed in these regulations.
71 8307.3 Definitions.
A. The following words and terms used in this regulation shall have the respective meanings ascribed to them as follows:
1. "Firm" means any person, partnership, corporation, association, or governmental entity.
2. "Hydrostatic testing" means pressure testing by hydrostatic methods.
3. "Portable fire extinguisher" means a portable device containing powder, liquid, or gases which can be expelled under pressure for the purpose of suppressing or extinguishing a fire. Portable fire extinguishers shall comply with NFPA 10, Standard for Portable Fire Extinguishers, 1998 edition.
4. "Inspection" means a quick check to insure that a fully charged, operable extinguisher is available. This is done by seeing that it is in its designated place, that it has not been actuated or tampered with, and that there is no obvious or physical damage or condition to prevent operation.
5. "Maintenance" means a thorough check of the extinguisher to give maximum assurance that an extinguisher will operate effectively and safely. It includes a thorough examination and any necessary repair or replacement. It will normally reveal the need for hydrostatic testing.
6. "Recharging" means the replacement of the extinguishing agent and also includes the expellant for certain types of extinguishers.
7. "Servicing" includes one or more of the following:
a. maintenance;
b. recharging; or
c. hydrostatic testing.
8. "Citation" means a summons to appear before the State Fire Marshal as a result of a violation of any part or all of this regulation and may carry a monetary fine of up to $2,000.
9. "Fixed extinguishing system" means systems having predetermined flow rates, nozzle pressures, and quantities of extinguishing chemical. These systems have the specific pipe size, maximum and minimum pipe lengths, flexible hose specifications, number of fittings, and number and types of nozzles prescribed by a testing laboratory. The hazards protected by these systems are specifically limited as to type and size by a testing laboratory based upon actual fire tests. Limitations on hazards which can be protected by these systems are contained in the manufacturer's installation manual which is referenced as part of the listing. Systems shall comply with the applicable National Fire Protection Association Standards and its references as follows:
a. NFPA 11, Standards for Low Expansion Foam and combined agents, 1998 edition;
b. NFPA 11A, Standards for Mediumand HighExpansion Foam Systems, 1994 edition;
c. NFPA 12, Standards on Carbon Dioxide Extinguishing Systems, 1998 edition;
d. NFPA 12A, Standards for Halon 1301 Fire Extinguishing Systems, 1997 edition;
e. NFPA 12B, Standards for Halon 1211 Fire Extinguishing Systems, 1990 edition;
f. NFPA 17, Standards for Dry Chemical Extinguishing Systems, 1998 edition;
g. NFPA 17A, Standards for Wet Chemical Extinguishing Systems, 1998 edition;
h. NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations, 1994 edition;
i. NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 1996 edition; and
j. Additional or updated National Fire Protection Association Standards as adopted by the State Fire Marshal.
71 8307.4. Licensing Requirements: Fire Equipment Dealer Licenses.
A. Each firm installing or servicing fixed fire extinguishing systems, portable fire extinguishers, or hydrostatic testing shall be licensed. In the following table, the first two numerals shall identify license type, 02license. The second two numerals shall identify the class category.
1. License:
a. 0201Class A;
b. 0202Class B;
c. 0203Class C; and
d. 0204Class D.
B. Type and Class Category 0201: Class"A" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of fire extinguishers, including recharging carbon dioxide units; and to conduct hydrostatic tests on all types of fire extinguishers.
2. Requirements:
a. file application in the category 0201;
b. provide proof of public liability insurance for an amount not less than $100,000; and
c. satisfy minimum equipment requirements.
C. Type and Class Category 0202: Class "B" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of fire extinguishers, including recharging carbon dioxide units and conducting hydrostatic tests on water, water chemical, and dry chemical types of extinguishers only.
2. Requirements:
a. file application in the category 0202;
b. satisfy minimum equipment requirements; and
c. provide proof of public liability insurance for an amount not less than $100,000.
D. Type and Class Category 0203: Class "C" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of fire extinguishers, except recharging carbon dioxide units; and to conduct hydrostatic tests of water, water chemical, and dry chemical types of fire extinguishers only.
2. Requirements:
a. file application in the category 0203;
b. provide proof of public liability insurance for an amount not less than $100,000; and
c. satisfy minimum equipment requirements.
E. Type and Class Category 0204: Class "D" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of preengineered fire extinguishing systems.
2. Requirements:
a. file application in the category 0204;
b. satisfy minimum equipment requirements;
c. provide proof of public liability insurance for an amount not less than $100,000; and
d. provide proof of manufacturer's certification for each type of preengineered fire extinguishing system.
71 8307.5. Licensing Requirements: Fire Equipment Permits.
A. Each person installing or servicing fixed fire extinguishing systems, portable fire extinguishers, and hydrostatic testing shall be issued permits. In the following table, the first two numerals shall identify permit type, 04permit. The second two numerals shall identify class category.
1. Permit:
a. 0401Class A;
b. 0402Class B;
c. 0403Class C;
d. 0404Class D; and
e. 0405Class E.
B. Type and Class Category 0401: Class "A" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of fire extinguishers, including carbon dioxide units and to conduct hydrostatic tests on all types of fire extinguishers, including carbon dioxide units.
2. Requirements:
a. file application in the category 0401;
b. provide current photograph, minimum size requirement 2"' x 2"'; and
c. examination required.
C. Type and Class Category 0402: Class "B" Fire Equipment Dealer License. [FN1]
[FN1] State Register Volume 23, Issue No. 6, eff June 25, 1999, promulgated two subsections designated "C".
1. Definition: To service, recharge, repair, or install all types of fire extinguishers, including carbon dioxide units and to conduct hydrostatic tests on water, water chemical, and dry chemical types of extinguishers only.
2. Requirements:
a. file application in the category 0402;
b. provide current photograph, minimum size requirement 2"' x 2"'; and
c. examination required.
C. Type and Class Category 0403: Class "C" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of fire extinguishers except recharging carbon dioxide units; also to conduct hydrostatic tests on water, water chemical, and dry chemical types of extinguishers only.
2. Requirements:
a. file application in the category 0403;
b. provide current photograph, minimum size requirement 2"' x 2"'; and
c. examination required.
D. Type and Class Category 0404: Class "D" Fire Equipment Dealer License.
1. Definition: To service, recharge, repair, or install all types of preengineered fire extinguishing systems.
2. Requirements:
a. file application in the category 0404;
b. provide current photograph, minimum size requirement 2"' x 2"';
c. examination required; and
d. provide a current manufacturer's training certificate.
E. Type and Class Category 0405: Class "E" Fire Equipment Permit
1. Definition: An apprentice may perform the services only under direct supervision of a person holding a valid permit under this subarticle and who works for the same firm as the apprentice. An apprentice permit is valid for one year from the day of issuance.
2. Requirements:
a. file application in the category 0405; and
b. provide current photograph, minimum size requirement 2"' x 2"'.
71 8307.6. Licensing Requirements: For Firms Performing Hydrostatic Testing.
Each firm performing hydrostatic testing of fire extinguishers manufactured according to the specifications of the United States Department of Transportation (DOT) shall be required to possess a valid license issued by the State Fire Marshal. All hydrostatic testing of fire extinguishers shall be performed per the appropriate DOT standards and NFPA standards.
71 8307.7. Types of Equipment.
All portable fire extinguishers and fixed extinguishing systems which are required by these regulations shall be listed by Underwriters' Laboratories, Inc., or approved by Factory Mutual and carry an Underwriters' Laboratories or manufacturer's serial number. These listings, approvals, and serial numbers may be stamped on the manufacturer's identification and instructions plate or on a separate Underwriters' Laboratories or Factory Mutual plate soldered or attached to the extinguisher shell in some permanent manner.
71 8307.8. Installation and Maintenance Procedures.
All fire extinguishers and preengineered systems covered under this subarticle and required by these regulations shall be installed and maintained per the applicable NFPA standards as referenced in 718307.3; Equipment shall be inspected, serviced, and maintained per the manufacturer's maintenance procedures.
71 8307.9. Permit Requirements.
Each individual actually performing the work of servicing, recharging, repairing, installing, or testing fire extinguishers or preengineered systems shall possess a valid permit issued by the Office of State Fire Marshal. Permittees shall be limited to specific type of work performed dependent upon the class of permit held. A license or permit issued under this subarticle shall not be transferable.
71 8307.10. Minimum Equipment and Facility Requirements for Fire Equipment Dealer License.
Office of State Fire Marshal
Minimum Equipment and Facility Requirements For Fire Equipment Dealer License
REQUIRED FOR MINIMUM EQUIPMENT AND FACILITIES REQUIRED CLASS
A 1. Adequate hydrostatic test equipment for high pressure testing and calibrated cylinder.
A 2. Adequate equipment for test dating high pressure cylinders (over 900 psi). Die stamps must be a minimum of 1/4 inch.
A 3. Clock with sweep secondhand on or close to hydrostatic test apparatus.
A B 4. CO2 receivercascade system CO2 for proper filling of CO2 extinguishers.
A B 5. Scales graduated in 1/8 ounce or gram weight if refilling CO2 cartridges.
A B C D 6. Approved drying method for high and low pressure cylinders.
A B C D 7. Proper wrenches for nonserrated jaws or valve puller, hydraulic or electric.
A B C D 8. Adequate inspection light.
A B C D 9. Low pressure test apparatus.
A B C D 10. Low pressure hydrostatic test labels as approved by National Fire Protection Association Pamphlet 10.
A B C D 11. Scales graduated in 1/4 ounce for weighing CO2 cartridges.
A B C D 12. Accurate weighing scales for extinguisher inspection and filling.
A B C D 13. Adequate vise 6inch minimum (chain or bench).
A B C D 14. Facilities for proper storage or dry chemical.
A B C D 15. Facilities for leak testing of pressurized extinguishers.
A B C D 16. Nitrogen with regulator and indicator. Regulator not to exceed 1500 psi minimum 500 psi. If air used in pressurization, it must be dry bottle storage.
A B C 17. Adapters, fittings, and sufficient tools and equipment for properly servicing and/or recharging all extinguishers being serviced and recharged.
A B C D 18. Adequate safety cage (in shop) for hydrostatic testing of low pressure cylinders.
D 19. Onefourth pound graduated scales minimum 150 pounds for weighing chemical recharging.
D 20. Cable crimping tool (where required).
D 21. Cocking lever (where required).
D 22. Pipe vise, dies, reamer, etc.
D 23. Adequate stock and supply of fuse links, proper elbows, and nozzles for system which is being installed.
D 24. Adequate supply of dry chemical in proper storage.
D 25. At the investigator's request, dealer should produce UL approved installation service manual for any system the investigator has prior knowledge is being serviced or installed by the license holder.
71 8307.11. Exceptions.
A. The provisions of this subarticle do not apply to the following:
1. filling or charging of a portable fire extinguisher by the manufacturer prior to its initial sale;
2. installation or servicing of water sprinkler systems installed per NFPA 13; and
3. firms engaged in the retailing or wholesaling of portable fire extinguishers as defined in Regulation 718307.3 but not engaged in the installation or recharging of them.
71 8307.12. Applications; Hearings on Licenses and Permits.
A. Applications for licenses and permits shall be made per these regulations.
B. An applicant for a license of any class shall meet all of the following requirements before receiving a license by the State Fire Marshal:
1. The applicant has submitted to the State Fire Marshal proof of insurance providing coverage for comprehensive general liability for bodily injury and property damage, products liability, completed operations, and contractual liability. The coverage insurance companies shall be licensed to conduct business in South Carolina. The State Fire Marshal shall adopt rules providing for the amounts of such coverage, but such amounts shall not be less than $100,000 for Class "A," "B," "C," or "D" license holders, and providing that an insurer providing such coverage shall notify the State Fire Marshal of any change in coverage for any class of license; and
2. The State Fire Marshal or a person designated by him has by inspection determined that the applicant possesses the equipment required for the class of license sought. The State Fire Marshal shall give an applicant a reasonable opportunity to correct any deficiencies discovered by inspection; and
3. The person who signed the application has passed, with a grade of at least seventy percent, a written and practical examination testing his knowledge of the rules and statutes regulating the activities authorized by the license, and demonstrating his knowledge and ability to perform those tasks in a competent, lawful, and safe manner. Examinations shall be developed and administered by the State Fire Marshal.
C. The State Fire Marshal, upon request, shall conduct hearings or proceedings concerning the suspension, revocation, or refusal to issue or renew licenses, apprentice permits, or approvals of testing laboratories issued under this subarticle or the application to suspend, revoke, refuse to renew, or refuse to issue the same.
D. An applicant, registrant, licensee, or permit holder whose license or permit has been refused or revoked under this subarticle, except for failure to pass a required written examination, shall not file another application for a license or permit within one year from the effective date of the refusal or revocation. After one year from that date, the applicant may reapply, and in a public hearing, show good cause why the issuance of his license or permit does not hinder public safety and health.
E. A person whose license to service portable fire extinguishers or to install or service fixed fire extinguishing systems has been expired or revoked must retake and pass the required written examination before a new license may be issued.
F. If a license has been expired for two years or longer, the license shall not be renewed. A new license shall be obtained by complying with the requirements and procedures for obtaining an original license. At least thirty days before the expiration of a license, the State Fire Marshal shall send written notice of the impending license expiration to the licensee at his or its last known address. This subsection shall not be construed to prevent the denying or refusing to renew a license under applicable law or regulations of the State Fire Marshal. Note: All licenses and permits shall expire on January 31, annually.
G. The State Fire Marshal shall send notice to each examinee of the results of the examination, not later than the thirtieth day after the day on which a licensing examination is administered under this subarticle. If an examination is graded or reviewed by a consultant testing service, the State Fire Marshal shall send notice to the examinees of the results of the examination within two weeks after the date on which the State Fire Marshal receives the results from the testing service. If the notice of the examination results will be delayed for longer than ninety days after the examination date, the State Fire Marshal shall send notice to the examinee of the reason for the delay before the ninetieth day. If requested in writing by a person who fails the licensing examination administered under this subarticle, the State Fire Marshal shall send to the person an analysis of the person's performance on the examination.
71 8307.13. Powers and Duties of the State Fire Marshal.
A. Powers and duties of the State Fire Marshal are:
1. to evaluate the applications of firms or individuals for a license to engage in the business of servicing portable fire extinguishers or installing fixed fire extinguishing systems;
2. to administer written examinations to ascertain the competency of applicants for a license to service portable fire extinguishers or install fixed fire extinguishing systems;
3. to issue licenses, permits, and apprentice permits which are required by this subarticle;
4. to evaluate the applications of firms seeking approval as testing laboratories for portable fire extinguishers;
5. to suspend or revoke licenses and permits for cause; and
6. to administer these regulations and supervise personnel in carrying out the requirements of this regulation.
71 8307.14. Certain Acts Prohibited.
A. No person or firm shall do any of the following:
1. Engage in the business of servicing portable fire extinguishers without a valid and current license;
2. Engage in the business of installing or servicing fixed fire extinguishing systems without a valid and current license;
3. Service portable fire extinguishers or service or install fixed fire extinguishing systems without a valid and current license;
4. Perform hydrostatic testing of portable fire extinguishers manufactured per the specifications and requirements of the United States Department of Transportation without a valid and current hydrostatic license;
5. Obtain or attempt to obtain a license or permit by fraudulent representation;
6. Service portable fire extinguishers or service or install fixed fire extinguishing systems contrary to the provisions of these regulations;
7. Service or hydrostatic test a fire extinguisher that does not have the proper identifying labels;
8. Sell, service, recharge, or have for use any of the following types of fire extinguisher:
a. Carbon tetrachloride;
b. Chlorobromomethane;
c. Dibromodifluoromethane;
d. Dichlorodifluoromethane;
e. Azeotropic chloromethane;
f. 1, 2 dibromo2chloro1, 1, 2 trifluoroethane;
g. 1, 2 dibromo2, 2difluoroethane;
h. Methyl bromide;
i. Ethylene dibromide;
j. Hydrogen bromide;
k. Methylene bromide;
l. Bromodifluoromethane; or
m. Any other toxic or poisonous vaporizing liquid fire extinguishers; and
9. Directly or through an agent sell, offer for sale, or give in this state any make, type, or model of fire extinguisher, either new or used, unless such make, type, or model of extinguisher has first been tested and is currently approved or listed by Underwriters' Laboratories, Inc., Factory Mutual Laboratories, Inc., or other nationally recognized testing laboratory whose testing procedures used for approval in the listing of portable fire extinguishers are acceptable to the State Fire Marshal, and unless such extinguisher carries an Underwriters' Laboratories, Inc., or manufacturer's serial number. The serial number shall be permanently stamped on the manufacturer's identification and instruction plate.
71 8307.15. Cease and Desist Orders; Notice to Correct Hazardous Conditions.
When the State Fire Marshal shall have reason to believe that any person is or has been violating any provisions of this regulation or any rules or regulations adopted and promulgated pursuant thereto, he or his designated agent may issue and deliver to such person an order to cease and desist such violation or to correct such hazardous condition.
71 8307.16. Suspension or Revocation of License or Permit.
A. The license of any company or individual may be suspended or revoked because of failure to comply with the terms of any order to correct violations within the specified abatement period or for failure to comply with any cease and desist orders. A license may be suspended for a period not to exceed one year from the date of license suspension. A license may be revoked for a period not to exceed two years from the date of license revocation.
B. In addition, a license may be suspended or revoked where the licensee is found to have:
1. rendered inoperative a fire extinguisher or preengineered system which is required by any rule of the State Fire Marshal, except during such time as the extinguisher or preengineered system is being inspected, serviced, or recharged;
2. falsified any records required to be maintained by this chapter or rules adopted thereto;
3. improperly serviced, recharged, repaired, tested or inspected a fire extinguisher or preengineered extinguishing system;
4. allowed another person to use his permit or license number or used a license or permit number other than the licensee's or permittee's valid license or permit number; or
5. obliterated the serial number on a fire extinguisher for purposes of falsifying service records.
71 8307.17. Responsibility of Equipment Manufacturer.
All manufacturers of portable fire extinguishers and fixed fire extinguishing systems doing business in South Carolina shall be required to provide to the State Fire Marshal all technical information as well as installation instructions that may apply to their systems and equipment sold, installed, and serviced in South Carolina. This technical information shall include design revisions and updating information on systems sold in South Carolina.
71 8307.18. Penalties.
The State Fire Marshal authorizes any Deputy State Fire Marshal or Certified Resident State Fire Marshal to issue a citation for each offense to any person, firm, or corporation licensed under these regulations who has violated any provision of this subarticle.
71 8308. Fire Safety: Construction and Operation of Local Detention Facilities.
71 8308.1. Application.
These regulations shall apply to the construction and operation of all local detention facilities, regardless of intended capacity. Facilities constructed on or before the effective date of these regulations are exempt from the requirements contained therein.
71 8308.2. Definitions.
A. "SBC" means the Standard Building Code, adopted in 718300.9.
B. "NFPA" means the National Fire Protection Association.
C. "Local detention facility" means any municipal, county, or multijurisdictional overnight lockup, jail, prison camp, or prison where one or more persons are held for more than six hours.
D. "UL" means Underwriters' Laboratories, Inc.
71 8308.3. Policy.
Consistent with the requirements of these regulations, each newly constructed and opened local detention facility shall:
1. be equipped with and maintain necessary fire detection, control and protection equipment;
2. establish, in writing, procedures for the prevention of, control of, and response to fires;
3. ensure that all facility staff members are trained in the use of fire detection, control, and protection equipment.
71 8308.4. Fire Detection Equipment.
A. Each local detention facility shall have installed and maintained a smokeactivated fire detection system that meets the requirements of NFPA 72, 1996 edition, for that type of fire detection system.
B. The smokeactivated fire detection system installed in a local detention facility shall:
1. be equipped with a sufficient number of manually operated signaling devices, with at least one on each floor, to ensure that an auxiliary means of activating the system is available; and
2. be designed and installed so as to detect fire in its initial stage in all areas of a local detention facility and upon such detection to automatically activate an audible signal, distinct from all signals of other sounding devices used in the vicinity, to warn all persons within a local detention facility in the event of fire or other emergency.
71 8308.5. Fire Control Equipment.
A. Standpipe Systems.
1. Each local detention facility two or more stories and exceeding 50 ft. in height shall install and maintain a Class III standpipe system per NFPA 14.
2. Any standpipe system installed pursuant to this section shall:
a. be designed and installed so that all facility areas can be quickly reached by an effective stream of water;
b. be designed to furnish heavy hose streams for severe fires, and firstaid streams to control incipient fires;
i. (As used in this section, the term heavy hose means hose which is 2 1/2 "' in diameter. It is not necessary that such hose be installed or maintained within a local detention facility;)
ii. (As used in this section, the term firstaid means hose which is 1 1/2 "' in diameter; such hose shall be immediately available for use in the facility by staff members and local fire fighter agencies.)
c. include a clear indication of the location of all standpipe system outlets and equipment;
d. have a reliable and adequate source of water sufficient to maintain an effective flow for a minimum of thirty minutes; and
e. have fire department connections with siamese feature for the injection of additional water at appropriate pressure into the standpipe system.
B. Sprinkler System.
1. Each local detention facility shall have installed and maintained an automatic sprinkler system per NFPA 13.
C. Each local detention facility shall install and maintain a sufficient number of fire extinguishers as required by NFPA 10. Such fire extinguishers shall:
1. be easily accessible for emergency use;
2. be maintained in a fully charged and operable condition;
3. not exceed 40 lbs. in gross weight;
4. if maintained in a facility area which contains electrical equipment, flammable liquids, solvents, paints or petroleumbased products, be of the carbon dioxide or multipurpose dry chemicaltype or other types as approved in NFPA 10;
5. if maintained in a facility area which contains wood, paper, cloth or rubbish, be of the multipurpose dry chemical or water type; and
6. not be of the soda and acid type.
71 8308.6. Fire Detection, Control, and Protection Equipment Specifications and Installation.
All fire detection, control, and protection equipment installed in a local detention facility shall be maintained per the requirements of the applicable NFPA standard. Such conformances shall be determined by the Resident Fire Marshal with the assistance of the Office of State Fire Marshal's Office and based on guidelines issued by the Office of State Fire Marshal.
71 8308.7. Hazardous Areas.
All hazardous areas, including boiler rooms, laundries, kitchens, storage rooms, paint shops, and trash rooms, shall be protected by proper separation or automatic extinguishing equipment to prevent spread of fire.
71 8308.8. Prohibition of Polyurethane Products.
Use of polyurethane products in the secured interior portions of local detention facilities is prohibited.
71 8308.9. Fire Retardant Paint.
All paint used within the secured portions of local detention facilities shall be fire retardant at least to the extent that, if applied to Douglas Fir and other tested combustible surfaces, it reduces flame spread to a flame spread classification value of 25 or less, and has a smoke developed rating not exceeding 450 when tested per ASTM E84.
71 8308.10. Minimum Requirements.
Except as provided by more stringent requirements included in these regulations, the minimum standards for new construction shall be the SBC for Group I, Restrained Occupancies.
71 8308.11. Emergency Fire Plans and Procedures.
The chief administrative officer of the local detention facility shall:
1. establish and maintain contact with a local fire fighting agency or other fire fighting authority;
2. ensure that a local fire fighting agency or other fire fighting authority shall, at a minimum, be familiar with:
a. the physical plant of the local detention facilities; and
b. the location and type of fire detection, control, and protection equipment available and maintained within the facility;
3. establish, in conjunction with a local fire fighting agency or other local fire fighting authority, an emergency fire safety plan which shall be in writing and shall include, but not be limited to:
a. procedures for the detection and reporting of fires to the local fire fighting agency;
b. procedures for the immediate and safe and secure evacuation of all persons;
c. procedures for fire control and extinguishment;
4. require that each local detention facility shall have within the facility and available for use by the staff a number of selfcontained breathing apparatuses sufficient to equip all detention facility personnel working on a shift or seven, whichever is the smaller number;
5. ensure that weekly inspections of the facility are conducted by facility personnel for the purpose of detecting and alleviating potential fire hazards, and ensure that reports of such inspections and remedial action based on such inspections are maintained;
6. ensure that all fire detection, control, and protection equipment maintained within the facility is inspected and tested at least every six months or per the recommendations of the manufacturer, whichever requires the more frequent inspection. Written records of such inspections shall be maintained for three years and shall include, but not be limited to:
a. the name of the inspecting person;
b. the date of the inspection;
c. the condition of the equipment; and
d. action taken to correct any deficiencies in the equipment.
7. The evacuation plan describing means and routes of exit for all persons within the facility shall be prominently posted throughout the facility.
71 8308.12. Fire Hazard Policies.
A. Each facility shall, by written regulation or policy, provide for the following:
1. controlled inmate access to smoking materials and matches;
2. prohibition of use of smoking materials and matches by intoxicated inmates and inmates who have been identified as presenting a high risk of suicide;
3. prohibition of inmate use of electrical extension cords and electrical equipment without express approval of the facility administrator and the resident fire marshal; and
4. prohibition of inmate use of polyurethane products, including mattresses and pillows.
71 8308.13. Training.
A. All facility staff members shall:
1. be provided with a written copy of the facility emergency fire plans and fire hazard policies;
2. be tested quarterly in the execution of the emergency fire plan;
3. be given preservice and inservice training concerning fire hazard policies.
71 8308.14. Reporting.
Any incident of fire shall be reported immediately to the local fire fighting agency and shall be reported to the State Department of Corrections and the Office of State Fire Marshal within 24 hours of such incident.
71 8309. Fire Safety: Existing Local Detention Facilities.
71 8309.1. Application.
These regulations shall apply to all local detention facilities already constructed or approved for construction before May 29, 1991.
71 8309.2. Definitions.
A. "SBC" means the Standard Building Code, adopted in 718300.9.
B. "NFPA" means the National Fire Protection Association.
C. "Local detention facility" means any municipal, county, or multijurisdictional overnight lockup, jail, prison camp, or prison where one or more persons are held for more than six hours.
D. "UL" means Underwriters' Laboratories, Inc.
71 8309.3. Policy.
A. Consistent with the requirements of these regulations, each local detention facility shall:
1. be equipped with and maintain necessary fire detection, control, and protection equipment;
2. establish in writing procedures for the prevention of, control of, and response to fires; and
3. ensure that all facility staff members are trained in the use of fire detection, control and protection equipment.
71 8309.4. Fire Detection Equipment.
A. Each local detention facility shall have installed and maintained a smokeactivated fire detection system that meets the requirements of NFPA 72, 1996 edition, for that type of fire detection system.
B. The smoke activated fire detection system installed in a local detention facility shall:
1. be equipped with a sufficient number of manually operated signaling devices to ensure that an auxiliary means of activating the system is available; and
2. be designed and installed so as to detect fire in its initial stage in all areas of a local detention facility and upon such detection to automatically activate an audible signal, distinct from all signals of other sounding devices used in the vicinity, to warn all persons within a local detention facility in the event of fire or other emergency.
71 8309.5. Fire Control Equipment.
A. Standpipe Systems.
1. Each local detention facility two or more stories and exceeding 50 ft. in height shall install and maintain a Class III standpipe system per NFPA 14.
2. Any standpipe system installed pursuant to this section shall:
a. be designed and installed so that all facility areas can be quickly reached by an effective stream of water;
b. be designed to furnish heavy hose streams for severe fires, and firstaid streams to control incipient fires;
i. (As used in this section, the term heavy hose means hose which is 2 1/2 "' in diameter. It is not necessary that such hose be installed or maintained within a local detention facility.)
ii. (As used in this section, the term firstaid means hose which is 1 1/2 "' in diameter. Such hose shall be immediately available for use in the facility by staff members and local fire fighting agencies.)
c. include a clear indication of the locations of all standpipe system outlets and equipment;
d. have a reliable and adequate source of water sufficient to maintain an effective flow for a minimum period of 30 minutes; and
e. have fire department connections with Siamese feature for the injection of additional water at appropriate pressure into the standpipe system.
B. Each local detention facility shall install and maintain a sufficient number of fire extinguishers as required by NFPA 10. Such fire extinguishers shall:
1. be easily accessible for emergency use;
2. be maintained in a fully charged and operable condition;
3. not exceed 40 lbs. in gross weight;
4. if maintained in a facility area which contains electrical equipment, flammable liquids, solvents, paints or petroleumbased products, be of the carbon dioxide or multipurpose dry chemical type or other types as approved in NFPA 10;
5. if maintained in a facility area which contains wood, paper, cloth or rubbish be of the multipurpose dry chemical or water type; and
6. not be of the soda and acid type.
C. Each local detention facility shall have within the facility and available for use by the staff a number of selfcontained breathing apparatuses sufficient to equip all detention facility personnel working on a shift or seven, whichever is the smaller number.
71 8309.6. Fire Detection, Control and Protection Equipment Specifications and Installation.
All fire detection, control, and protection equipment installed in a local detention facility shall be maintained per the specification requirements of the National Fire Protection Association's National Fire Codes. Such conformances shall be determined by the resident fire marshal with the assistance of the Office of State Fire Marshal and based on guidelines issued by the Office of State Fire Marshal.
71 8309.7. Exits.
A. Means of egress shall consist of continuous and unobstructed paths of travel to the exterior of a building at all times. Means of egress shall not be permitted through kitchens, closets, restrooms and similar areas nor through adjacent tenant spaces.
B. Consistent with the requirements of subdivision C of this section, each local detention facility shall maintain at least two exits from each facility housing area.
C. Exits shall be so located that the distance from the most remote point in the floor area, room, or space served by them to the nearest exit, measured along the line of travel, shall not be so great as to create a hazard to human life in case of fire.
D. Where more than one exit is required, at least two shall be located as remote from each other as practicable and shall be so arranged and constructed to provide direct access in separate directions from any point in the area served and to minimize the possibility that both may be blocked by any one fire or other emergency condition.
E. Exits shall be:
1. clearly visible or the route to reach such exit conspicuously indicated;
2. illuminated;
3. exit doors shall be constructed so as to be unlocked from both the inside and the outside of the door by the facility staff, who shall have immediate access at all times to necessary keys or other unlocking mechanisms; and
4. kept clear and maintained in usable condition.
F. Each vertical way of exit and other vertical openings between floors of a facility shall be suitably enclosed or protected to afford reasonable safety to all persons while using such exits.
G. All required exit stairs shall be enclosed in onehour fire resistant construction.
71 8309.8. Hazardous Areas.
All hazardous areas, including boiler rooms, laundries, kitchens, storage rooms, paint shops, and trash rooms shall be protected by proper separation or automatic extinguishing equipment to prevent spread of fire.
71 8309.9. Prohibition of Polyurethane Products.
Use of polyurethane products in the secured interior portions of local detention facilities is prohibited.
71 8309.10. Fire Retardant Paint.
All paint used within the secured portions of local detention facilities shall be fire retardant at least to the extent that, if applied to Douglas Fir and other tested combustible surfaces, it reduces flame spread to a flame spread classifications value of 25 or less and has a smoke developed rating not exceeding 450 when tested per ASTM E84.
71 8309.11. Other Code Requirements.
Local detention facilities constructed under a building code shall, regarding any specific area of regulation, be required to comply with the applicable section of these regulations or of the construction building code, whichever is more stringent.
71 8309.12. Emergency Fire Plans and Procedures.
A. The chief administrative officer of each local detention facility shall:
1. establish and maintain contact with a local fire fighting agency or other fire fighting authority;
2. ensure that a local fire fighting agency or other fire fighting authority shall, at a minimum, be familiar with:
a. the physical plant of the local correctional facility; and
b. the location and type of fire detection, control, and protection equipment available and maintained within the facility;
3. establish, in conjunction with a local fire fighting agency or other local fire fighting authority, an emergency fire safety plan which shall be in writing and shall include, but not be limited to:
a. procedures for the detection and reporting of fires to the local fire fighting agency;
b. procedures for the immediate and safe and secure evacuation of all persons; and
c. procedures for fire control and extinguishment;
4. ensure that weekly inspections of the facility are conducted by facility personnel for the purpose of detecting and alleviating potential fire hazards; and ensure that reports of such inspections and remedial action based on such inspections are maintained;
5. ensure that all fire detection, control, and protection equipment maintained within the facility is inspected and tested at least every 6 months or per the recommendations of the manufacturer, whichever requires the more frequent inspection. Written records of such inspections shall be maintained and shall include, but not be limited to:
a. the name of the inspecting person;
b. the date of the inspection;
c. the condition of the equipment; and
d. action taken to correct any deficiencies in the equipment.
6. the evacuation plan describing means and routes of exit for all persons within the facility shall be prominently posted throughout the facility.
71 8309.13. Fire Hazard Policies.
A. Each facility shall, by written regulation or policy, provide for the following:
1. controlled inmate access to smoking materials and matches;
2. prohibition of use of smoking materials and matches by intoxicated inmates and inmates who have been identified as presenting a high risk of suicide;
3. prohibition of inmate use of electrical extension cords and electrical equipment without express approval of the facility administrator and the local resident fire marshal (local fire safety inspector); and
4. prohibition of inmate use of polyurethane products, including mattresses and pillows.
71 8309.14. Training.
A. All facility staff members shall:
1. be provided with a written copy of the facility emergency fire plan and fire hazard policies;
2. be tested quarterly in the execution of the emergency fire plan;
3. be given preservice and inservice training concerning fire hazard policies; and
4. be trained in the use of selfcontained breathing apparatus.
71 8309.15. Reporting.
Any incident of fire shall be reported immediately to the local fire fighting agency and shall be reported to the State Department of Corrections and the Office of State Fire Marshal within 24 hours of such incident.
71 8310. Fire Safety: Renovation of Existing Local Detention Facilities.
71 8310.1. Review of Plans.
Plans for renovation (alterations, repairs, or rehabilitation) of local detention facilities shall be submitted to the Office of State Fire Marshal for approval regarding compliance with these regulations and other fire safety codes.
71 8310.2. Compliance with Regulations.
All renovation of local detention facilities shall, to the extent determined by the State Fire Marshal, comply with the requirements of these regulations for the construction of new local detention facilities.
71 8312. Proximate Audience Pyrotechnics.
A. Definitions. Note: The following terms are not necessarily inclusive of all of the terms used in the pyrotechnic special effect industry.
1. "Alternating current (ac)" means electrical current that reverses direction in a circuit at regular intervals. Almost all electrical current supplied from wall outlets or sockets is alternating current.
2. "Black match" means a fuse made from thread impregnated with black powder and used for igniting pyrotechnic devices.
3. "Blank cartridge" means a cartridge constructed from a cartridge case with a percussion primer and filled with various loads of smokeless powder or other propellant. Weapons using blank cartridges are often used in conjunction with bullet hits.
4. "Bridgewire" means a fine wire that either heats up or explodes when an electric current is applied. It is used to fire pyrotechnic devices.
5. "Bullet effect" means an effect intended to simulate a slug from a weapon striking a person or object.
6. "Bullet hit" means a small explosive charge attached to a person, to the body, or to an inanimate object to simulate a slug from a weapon striking a person or object.
7. "Color pot" means a tube containing pyrotechnic materials. It produces a colored flame when it is ignited.
8. "Colored smoke" means an aerosol of special dyestuffs of chemical reactants dispersed by pyrotechnic heat or explosion.
9. "Common fireworks" means any composition or device for producing a visible, audible, or both visible and audible effect by combustion, deflagration, or detonation and meets the definition of "common" or "special" fireworks as set forth in the United States Department of Transportation's Hazardous Materials Regulation, Title 49 Code of Federal Regulations Parts 173.88 and 173.100.
10. "Concussion flash powder" means flash powder intended to be used in a concussion mortar to produce a loud concussive effect.
11. "Day box" means a portable magazine used for immediate storage of pyrotechnic materials.
12. "Deflagration" means a rapid chemical reaction in which the output is sufficient to enable the reaction to proceed and be accelerated without input of heat from another source. Deflagration is primarily a surface phenomenon with most reaction products flowing away from the unreacted material along the surface at the supersonic velocity. The effect of a deflagration under confinement is an explosion. Confinement of the reaction increases pressure, rate of reaction, and temperature, and in some cases, can cause transition into a detonation.
13. "Det cord (primacord)" means a flexible detonating cord. It is a highly explosive material encased in a plasticcovered cord resembling a clothesline.
14. "Detonation" means an extremely rapid chemical reaction in which the pressure generated is sufficient to cause the formation of a shock wave, which acts to cause the reaction to proceed. Detonation is a phenomenon with reaction products flowing in the direction of unreacted materials at supersonic velocity. The effect of a detonation with or without confinement is an explosion.
15. "Detonator" means any devices containing an initiating or primary explosive that is used for initiating detonation. The term includes, but is not limited to, electric blasting caps (of instantaneous and delay types), blasting caps for use with safety fuses, detonating cord delay connectors, and nonelectric caps that use a detonating cord, shock tube, or any other replacement for electric legwires. A detonator may also be an explosive or device initiated by a primer and used to initiate another explosive that is less sensitive and larger.
16. "Direct current (dc)" means electrical current that flows in one direction. Most frequently, direct current is supplied by a battery.
17. "Explosion" means the rapid production of hot gasses at a high pressure as the result of a chemical reaction and the sudden release of the energy to cause strong dynamic stresses in the surroundings. The term usually relates to the effects of a detonation of initiating explosives and high explosives, but also applies to the effect of a deflagrating propellant explosive in certain circumstances such as heavy confinement. Explosion is also a mechanical phenomenon in which failure of the container results in sudden release of pressure from within a vessel.
18. "Explosive" means any chemical compound, mixture, or device whose primary or common purpose is to function by explosion. The term includes, but is not limited to, dynamite, black powder, pellet powder, initiating explosives, detonators, safety fuses, squibs, detonating cords, igniter cords, and igniters. The term "explosives" includes any material determined to be within the scope of Title 18, United States Code, Chapter 40, Importation, Manufacture, Distribution, and Storage of Explosive Materials, and also includes any material classified as a Class 1.1, Class 1.2, and Class 1.3 explosive by the Hazardous Material Regulations of the United States Department of Transportation.
19. "Fireworks" means any composition or device for producing a visible, audible, or both visible and audible effect by combustion, deflagration, or detonation, and which meets the definition of "common" or "special" fireworks as set forth in the United States Department of Transportation's Hazardous Material Regulation, Title 49, Code of Federal Regulations, Parts 173.88 and 173.100.
20. "First fire" means the ignited mixture used with pyrotechnic devices and loaded in direct contact with the main pyrotechnic charge. A pyrotechnic firstfire mixture is compounded to produce a high temperature and hot slag. The mixture must be readily ignitable and capable of igniting the underlying pyrotechnic charge.
21. "Lycopodium" means the spores produced by the genus of mosses called lycopodium. This powdery, organic, yellow material can be agitated and dispersed mechanically into a cloud and then ignited by a spark, pilot flame, or electrical heating device. Although not a pyrotechnic material, this material is used by special effects operators to produce fire effects or in conjunction with other pyrotechnics to create a special effect.
22. "MSDS(s)" means Material Safety Data Sheet(s).
23. "Motion picture" means, for the purposes of this item, any audiovisual work with a series of related images either on film, tape, or other embodiment, where the images shown in succession impart an impression of motion together with accompanying sound, if any, which is produced, adapted, or altered for exploitation as entertainment, advertising, promotional, industrial, or educational media.
24. "Nonelectric detonator" means a detonator that does not require the use of electric energy to function.
25. "Photoflash (photoflash powder)" means a loose pyrotechnic mixture that yields a very large amount of light for a small fraction of a second on exploding.
26. "Proximate audience" means an audience located closer to the pyrotechnics than allowed by NFPA 1123 (see below).
Minimum Radius of Display Site for Outdoor Display of Fireworks
Shell Size Minimum Radius of Display Site for Outdoor
Display of Fireworks
3 in. (76 mm) 140 ft. (43 m)
3 in. (76 mm) 210 ft. (64 m)
4 in. (102 mm) 280 ft. (85 m)
5 in. (127 mm) 350 ft. (107 m)
6 in. (152 mm) 420 ft. (128 m)
7 in. (178 mm) 490 ft. (149 m)
8 in. (203 mm) 560 ft. (170 m)
10 in. (254 mm) 700 ft. (214 m)
12 in. (305 mm) 840 ft. (256 m)
12 in. (305 mm) Approval of authority having jurisdiction
27. "Quick match" means black match that is encased in a loosefitting paper sheath. Although an exposed black match burns slowly, quick match burns extremely rapidly, almost instantaneously. Quick match is used in fuse for aerial shells and for simultaneous ignition of a number of pyrotechnic devices, such as lances in a grounddisplay piece.
28. "Safety fuse" means a flexible cord containing an internal burning medium by which fire or flame is conveyed at a constant and relatively uniform rate from the point of ignition to the point of use.
29. "Salute powder" see sonic flash.
30. "SCFM" means the South Carolina State Fire Marshal or his designee.
31. "Soft detonator" means a detonator with a higher velocity than a bullet, but with no metallic elements or jacket. This is essentially a blasting cap without metal jacket.
32. "Sonic flash (salute powder, extra fast flash, concussion flash powder)" means flash powder specifically formulated to produce a loud concussive effect.
33. "Sparkle flash powder" means a flash powder that produces a bright flash of light and a shower of sparks when it is ignited.
34. "Special fireworks" means large fireworks designed primarily to produce visible or audible effects by combustion, deflagration, or detonation. This term includes, but is not limited to, firecrackers containing more than 2 grains (130 mg) of explosive composition, aerial shells containing more than 40 grams of pyrotechnic composition, and other display pieces that exceed the limit for classification as "Common Fireworks." Special fireworks are classified as Class 1.3 by the United States Department of Transportation.
35. "Stars" means small masses of pyrotechnic compounds that are projected from aerial shells, mines, or roman candles. Stars burn while in the air, producing color or streamer effects.
36. "Theatrical flash powder" means a pyrotechnic material intended for use in theatrical shows. Theatrical flash powder produces a flash of light when ignited. Typical theatrical flash powders burn more slowly than salute powder and may also produce a shower of sparks. Theatrical flash powder is not intended to produce a loud report.
B. Exceptions: The following are exempt from these permits and licenses;
1. weapons used in enactments, when there is no projectile;
2. artillery field pieces used as salutes with no projectile; and
3. the use of model rockets outdoors by private individuals or clubs where no admission fee is charged.
C. Licenses and Permits for the Sale, Storage, and Use of Pyrotechnics.
1. Licenses for pyrotechnic operators authorize and place the responsibility for the handling, supervision, and discharge of any type or class fireworks or pyrotechnic device as may be permitted by the authority having jurisdiction, and establish that the operator is responsible for the training of his or her assistants in the safe handling, supervision, and discharge of these items and devices, in accordance with the following. Licenses are valid for one calendar year from the date of issue and must be renewed annually.
a. Pyrotechnic OperatorUnrestricted may conduct and take charge of all fireworks activity in connection with every kind of public fireworks display, whether commercial entertainment, experimental and other types of rockets, or special effects in motion picture, theatrical, and television production.
b. Pyrotechnic OperatorBasic Commercial may conduct and is restricted to all fireworks activities in connection with a commercial fireworks public display, including the determination that all mortars, set pieces, rocket launchers, and rockets are properly installed and that proper safety precautions have been taken to insure the safety of persons and property. Such operator shall have charge of all activities directly related to handling, preparing, and firing all fireworks at the public display, including the fixing of lift charges and quick match as needed for aerial shells.
c. Pyrotechnic OperatorRestricted Commercial may conduct and is restricted exclusively to the use and discharge of firecrackers and the use of other exempt fireworks in religious ceremonies, as may be permitted by the authority having jurisdiction.
d. Pyrotechnic OperatorRockets first class may conduct and is restricted to all activities in connection with research experiments, production, transportation, fuel loading, and launching of all types of experimental rockets. Such operator shall also be responsible for the actions and the conduct of all assistants.
e. Pyrotechnic OperatorRockets Second Class may conduct and is restricted to all activities in connection with research experiments, production, transportation, fuel loading and launching of all types of solid fuel experimental rockets only. Such operator shall also be responsible for the actions and conduct of all assistants.
f. Pyrotechnic OperatorRockets Third Class may purchase, transport, store and launch high power rockets. Experimental highpowered motors may only be imported, exported, and wholesaled by individuals or companies holding valid import, export, or wholesale licenses. Pyrotechnic Operator Rockets Third Class may only purchase highpowered rocket motors from licensed wholesalers.
g. Pyrotechnic OperatorMotion Picture Special Effects First Class may conduct and is restricted to the use, preparation, and use of all types of fireworks and special effects pyrotechnics, as may be permitted by the authority having jurisdiction, for the sole purpose of producing a visible or audible effect where and when such use is a necessary part of motion picture, television, theatrical or operatic production.
h. Pyrotechnic OperatorMotion Picture Special Effects Second Class may conduct and is restricted to the use of special effects, the loading of blank cartridges, colored fire, flash paper, smoke composition, the preparation and use of binary flash composition, and such other fireworks of whatever kind or class as may be permitted by the authority having jurisdiction.
i. Pyrotechnic OperatorMotion Picture Special Effects Third Class authorizes the loading of blank cartridge shells, and use of special effects, as may be permitted by the authority having jurisdiction, when under the direct supervision and control of a Pyrotechnic OperatorUnrestricted, Special Effects First or Second Class.
j. Pyrotechnic OperatorTheatrical authorizes the use of special effects, blank cartridges, colored fire, flash paper, flash smoke, composition, and the preparation and use of binary flash composition, as may be permitted by the authority having jurisdiction, in stage or theatrical productions only.
k. Pyrotechnic OperatorTheatrical Trainee authorizes the conducting of procedures permitted a Pyrotechnic OperatorTheatrical when under the direct supervision and control of a Pyrotechnic OperatorUnrestricted or a Pyrotechnic OperatorTheatrical.
l. Pyrotechnic OperatorPerformer is restricted to persons who perform before an audience, directly or indirectly, and may include magicians, comedians, still photographers, and others whose primary interest is in other than pyrotechnics. Such license is restricted to the use of blank cartridges, colored fire, flash paper, sparklers, and smoke composition, as may be permitted by the authority having jurisdiction, in connection with the production of theatricals and operas before a live audience in theaters, opera houses, television studios, night clubs, and similar occupations, or by the use of still photographers.
D. Display permits.
1. Permits shall be valid for the calendar period prescribed or until any condition of the permit application is changed.
2. A license or permit may be revoked, suspended, or denied by the State Fire Marshal because of, but not limited to:
a. noncompliance with any order written by the State Fire Marshal;
b. conviction of a crime of violence or any crime punishable by a term of imprisonment exceeding two years;
c. advocating or knowingly belonging to any organization or group which advocates violent overthrow of or violent action against the federal, state, or local government;
d. having or contracting physical or mental illness or conditions that in the judgment of the State Fire Marshal would make use or possession of pyrotechnics or explosive materials hazardous to the licensee or permittee and to the public;
e. violating the terms of the license or permit or essential changes in the conditions under which the license or permit was issued without prior approval of the State Fire Marshal;
f. violating the provisions of the law and regulations of Proximate Audience Pyrotechnics. However, except for violations considered an immediate threat to public safety, the State Fire Marshal may issue a notice of noncompliance and set a time limit to achieve compliance; and
g. giving false information or making a misrepresentation to obtain a license or permit.
3. Permits may be issued for:
a. one day to thirty consecutive days;
b. greater than thirty consecutive days to one hundred eighty consecutive days;
c. greater than one hundred eighty consecutive days to three hundred sixtyfive consecutive days; or
d. special, one performance, less than five effects, and an audience of less than twenty persons.
4. Applications:
a. Applications for permits shall be received in the Office of State Fire Marshal fifteen days prior to the performance date. Should the application be received less than fifteen days prior to the performance date, the application fee is doubled.
b. Applications for motion picture related licenses and permits shall be received in the Office of State Fire Marshal fifteen days prior to the performance date. Should the application be received less than fifteen days prior to the performance date, the application fee is doubled.
5. Fees.
a. Licenses or permits are required for the following. Should the applicant possess an equivalent license or permit issued by LLR, duplicates are not required. The SCFM shall determine equivalency. The fees for licenses and permits are:
i. Manufacture $1500.00
ii. Wholesaler/distributor $1000.00
iii. Jobber $ 400.00
iv. Importer and exporter $1500.00
v. Retailer $ 50.00
vi. Display one day to thirty consecutive days $ 300.00
vii. Display greater than thirty consecutive days to one $ 600.00 hundred eighty consecutive days
viii. Display greater than one hundred eighty consecutive $1000.00 days to three hundred sixtyfive consecutive days
ix. Special display, one performance, less than five $ 25.00 effects, and an audience of less than twenty persons
x. Pyrotechnic operator
a. Unrestricted $ 300.00
b. Basic commercial $ 75.00
c. Restricted commercial $ 50.00
d. Rockets, first class $ 50.00
e. Rockets, second class $ 50.00
f. Rockets, third class $ 50.00
g. Motion Picture Special effects, first class $ 250.00
h. Motion Picture Special effects, second class $ 200.00
i. Motion Picture Special effects, third class $ 100.00
j. Theatrical $ 200.00
k. Theatrical trainee $ 100.00
l. Performer $ 100.00
xi. Magazines $ 50.00
xii. Circuit tester approval $ 10.00
xiii. Firing device approval $ 10.00
6. Enforcement.
a. The SCFM or any authority having jurisdiction may enforce these laws and regulations.
b. It shall be the responsibility of the facility manager, the permittee, and the licensee to insure that the requirements of the law and regulations governing pyrotechnics used before a proximate audience are complied with.
7. Penalties.
a. Any person who violates any provision of these laws and regulations will purchase the appropriate permit, pay the appropriate license fee, if any are required, and be subject to the following:
i. S.C. Code Ann. 2336170, 1976, as amended.
ii. S.C. Code Ann. 2335150, 1976, as amended.
8. Confiscation, storage, or disposal of pyrotechnic and explosive materials used for proximate audience displays by the State Fire Marshal shall comply with S.C. Code Ann. 2336110, 1976, as amended.
9. Regulation of the use of pyrotechnic materials before a proximate audience by local governments.
Nothing contained in these regulations shall affect any existing ordinances or regulations pertaining to the use of pyrotechnic materials before a proximate audience of any county or incorporated city or town which are not less restrictive than the provision of this chapter and regulations or affect, modify, or limit the power of the county or incorporated city or town to adopt ordinances and regulations pertaining to the use of pyrotechnic materials before a proximate audience within the county or corporate limits.
10. Qualifications of pyrotechnic operators.
a. No person who has not actively participated in the setup and loading of at least five proximate audience performances in which pyrotechnic special effects were used shall be granted a license. (At the option of the issuing office, an alternative number shall be permitted to be substituted.)
b. No person shall be granted a license who has not met the requirements of paragraph A above and at least one of the following requirements:
i. successfully completed a comprehensive written examination covering this code and state laws pertaining to the display of proximate audience pyrotechnic special effects;
ii. received a competency certificate from a national organization that promotes the safe use of pyrotechnic special effects and is approved by the SCFM;
iii. has been licensed for the use of pyrotechnic special effects by another state approved by the SCFM; or submits
iv. a letter from the authority having jurisdiction and a licensed operator stating their satisfaction as to the qualifications of the operator and is approved by the SCFM.
11. The SCFM shall designate the type of pyrotechnic operators license issued on an individual basis.
12. Provisions for license renewal. A license shall be granted upon review of the applicant's record, proving active participation in at least three pyrotechnic special effect performances during the period covered by the license being renewed, and that these displays were operated in a safe manner and approved by the SCFM. The proximate audience displays can be either indoor or outdoor.
E. Insurance requirements.
1. Liability insurance in the amount of $500,000 shall be provided by the permittee. The permittee shall furnish a certificate of insurance or provide proof of selfinsurance in this amount.
2. Liability insurance in the amount of $1,000,000 shall be provided by any permittee involved with motion picture productions. Motion picture companies employing this person(s) shall list the State of South Carolina and its agents as additional insureds.
F. Inspections.
1. The authority having jurisdiction who is required to judge the safety of any production or rehearsal shall inspect to insure compliance of the following requirements. This is a minimum inspection and the authority having jurisdiction may add to these requirements. The SCFM may photograph or videotape any or all parts of these inspections.
a. Access:
i. fire lane kept clear;
ii. hydrants not blocked;
iii. fire department connections clear;
iv. standpipe connections clear;
v. at least two fire extinguishers in accordance with NFPA 10 are provided;
vi. extinguishing equipment charged and in good working order; and
vii. warning signs.
b. Exits:
i. all designated exits clear; and
ii. exits visible.
c. Pyrotechnic materials and devices:
i. proper and current license in the possession of the pyrotechnic operator;
ii. permit on site;
iii. fire department briefed on proposed activity;
iv. alternate means of protection provided; and
v. proper ventilation.
d. Electrical:
i. electric wire and connections in good condition;
ii. appropriate power supply; and
iii. pyrotechnic firing mechanism in good working order.
e. Flameproofing:
i. set and scenic materials appropriately treated for flame retardance in accordance with NFPA 701;
ii. burlap and other protective materials used for rigging treated for flame retardance in accordance with NFPA 701.
G. Circuit testers and firing devices.
1. Circuit testers and firing devices which are not blasting certified shall be certified annually by a testing facility approved by the SCFM.
i. Circuity testers shall supply no more than 25 mA of current and measure resistance in ohms; and
ii. Firing devices shall be rated as to the number of effects it will function in a series circuit and the number it will function in a parallel circuit.
H. Storage of special effects pyrotechnics and other material.
1. All classes of explosives shall be stored in accordance with the South Carolina Explosive Control Act or Title 27 Code of Federal Regulations, Subpart K.
2. All other pyrotechnic materials shall be stored in accordance with the appropriate NFPA standard.
I. Posting of permit.
1. Three copies of the permit package shall be posted, one on each side of the stage and one at the control site. The permit package shall contain a copy of the permit, Certificate of Insurance, and the MSDS(s).
J. Fire Protection.
1. The authority having jurisdiction may require the permittee to furnish fire support personnel other than local firefighters.
2. The permittee shall demonstrate to the authority having jurisdiction a proficiency in the use of all classes of fire extinguishers and standpipe system provided.
3. There shall be one person who is approved by the authority having jurisdiction assigned to each fire extinguisher.
4. The permittee shall furnish a fire watch during the times the special effects materials have been removed from storage and/or magazines and the conclusion of the performance. This person shall be identified by an orange shirt or vest with threeinch white letters on the front and back stating FIRE WATCH.
(For motion picture productions, the method for identifying the FIRE WATCH person on site shall be a mutually agreed upon means of designation between the State Fire Marshal, the permittee, and the First Assistant Director.)
5. Automatic fire alarm systems are required. The smoke detectors shall be zoned so that the areas affected by special effects smoke can be zoned out.
6. An override switch shall be provided at the firing point and a second switch and flashing light in the control room to shut off stage sound and make the public address system available for evacuation instructions.
K. Records.
1. Magazine log shall be available for inspection during normal work hours, 1 hour before, and 1 hour after each performance.
2. A true copy of all purchase and sales records of all special effects material to include Department of Transportation (DOT) manifest, shall be sent to the SCFM within five days of the transaction.